Busbar tap-off unit
www.janitza.de
56
10.8 Scope of delivery
This supplementary user manual for the busbar
tap-off unit assumes that a BD2 busbar system is
already installed.
Item
Scope of delivery (designation)
1
BD2 busbar tap-off unit,
AKM 96RM-E, AKM 96-PA or AKM 806
2
Dummy plug to close the unused outgoing power
feeder
Not
included in delivery:
·Screw connections for the load output.
·Cable connectors for the network connection
(Ethernet and RS-485).
·Cable connectors for the digital input (with corre-
sponding option).
INFORMATION
·All supplied options and design variants of your
busbar tap-off unit are described on the delivery
note.
·See separate document for parts list!
INFORMATION
Please note!
The size of the busbar tap-off unit depends on the
variants (see „Technical data“ on page 72)!
The feed of the 125 A version of the busbar tap-off
unit is equipped with a cover disconnector, which
disconnects the tap-off unit from the live busbar
system when the cover is opened. This allows
shockproof working on the installed tap-off unit.
With all other versions of the busbar tap-off unit,
there is no disconnection when the cover is
opened! In this case, a finger-safe design of the
busbar tap-off unit provides protection against
contact.
AKM 806 - Busbar tap-off unit with UMG 806 measurement device
AKM 806 - 125
AKM 806 - 250
AKM 806 - 400
AKM 806 - 530
Maximum output current
125 A
250 A
400 A
530 A
Current transformer
150 A / 5 A Cl.1
250 A / 5 A Cl.1
400 A / 5 A Cl.1
600 A / 5 A Cl.1
Current measurement
3P+N
Ethernet interface (RJ45
socket)
RS-485 interface
(1x socket, 1x plug)
Circuit breaker
(measurement device
fuse)
Temperature measure-
ment (PT 100 sensor)
RCM measurement
Type A
RCM measurement
1)
Type A/B/B+
-
-RCMplus -
optional
-RCMplus -
optional
-RCMplus -
optional
Current transformer for
RCM measurement
CT-AC RCM 35N
CT-AC RCM 80N
CT-AC RCM 110N
CT-AC RCM 140N
1) ... For an RCM measurement according of type A/B/B+, the AKM also requires the RCM 202-AB measurement device.