13
ProData II
Connection of a ProData 2 with gateway function to
a PC via Ethernet.
In this installation, the ProData 2 can forward queries
(e.g. from the GridVis software) to a Modbus slave
device. However, it CANNOT query Modbus slave
devices independently!
RS485 mode: Gateway; address 3=1
(twisted patch cable)
UMG 103
(Modbus slave)
UMG 104
(Modbus slave)
ProData 2
(Gateway)
Connecting a ProData 2 as a Modbus slave device.
The ProData 2 is configured as a Modbus slave.
Communication to the ProData 2 can take place directly
via Ethernet or via the Modbus master.
The ProData 2 cannot forward any Ethernet queries to
a Modbus slave device!
RS485 mode: Slave; address 3=0
ProData 2
(Modbus slave)
UMG 103
(Modbus slave)
UMG 104
(Modbus slave)
UMG 604
(Modbus master)