14
ProData II
Installation
Position of installation
The ProData 2 is designed for fixed installation in low
voltage switching devices. It is assembled on a 35 mm
mounting rail in accordance with DIN EN 60715. Can be
installed in any mounting position.
Installation
Supply voltage
The ProData 2 requires a supply voltage to operate.
The supply voltage is connected to the front side
of the device via a 2-pin plug-in terminal.
Before connecting the supply voltage, make sure that
the voltage and frequency correspond to the details
on the ratings plate.
The supply voltage must be connected through a UL/
IEC approved fuse (6 A, type CC) or a circuit breaker
(6 A, C.Char).
m
• If installed in a building, a disconnector
or circuit breaker must be provided for
the supply voltage.
• The disconnector must be installed
near the device and easily accessible
to the user.
• The switch must be marked as the circuit
breaker for this device.
• Voltages which are over the permitted
voltage range can destroy the device.