36
ProData II
Rate conversion
A tariff selection of 1 to 8 can be assigned to each digital
input; the tariffs can be activated via digital inputs 1-8,
via a Modbus and via the timer. Each input can be reset
individually via the GridVis software.
0
0
0
0
0
1
Tariff 8 (0 = not set)
Tariff 7 (0 = not set)
Tariff 6 (0 = not set)
Tariff 5 (0 = not set)
Tariff 4 (0 = not set)
Tariff 3 (0 = not set)
Tariff 2 (1 = tariff set)
Tariff 1 (0 = not set)
0
0
0
0 1 2 3 4 5 6 7
Bit:
The tariff conversion via Modbus takes place via
addresses 1940 (for digital input 1) to 1954 (digital
input 16). The relevant tariff is to be selected by setting
or deleting bits 0 to 7. Only the highest-value tariff is
evaluated.
Tariff
T1
T2
T3
T4
T5
T6
T7
T8
Bit
0
1
2
3
4
5
6
7
Input
Address
1
1940
0
1
0
0
0
0
0
0
2
1941
0
0
0
0
0
0
0
0
...
...
15
1954
0
0
1
0
0
0
0
0
Bit-by-bit representation of the tariff conversion
Example: For digital input 1, tariff 2 is set, for input 15,
tariff 3 is set.
In addition to the tariff conversion, the individual tariffs
are to be activated via Modbus addresses 1700 (tariff 1)
to 1707 (tariff 8).
Address
Tariff
1700
1
0 = tariff deactivated, 1 = tariff activated
1701
2
0 = tariff deactivated, 1 = tariff activated
1702
3
0 = tariff deactivated, 1 = tariff activated
...
...
...
1707
8
0 = tariff deactivated, 1 = tariff activated
Example of tariff 2 set: If the value is set to address 1940,
the tariff conversion for digital input 1 applies.