94
UMG 96RM-P/-CBM
Status
Status description
EEE
bAt
321
• Battery capacity is <85%
• Operator confirmation required
• Message appears weekly after confir-
mation
• Battery should be replaced
EEE
bAt
322
• Battery capacity is <75%
• Battery capacity is too low
• Can only be detected after resumption
of mains power
• Battery should be replaced
EEE
bAt
330
• Battery capacity OK
• Message can be acknowledged
• Clock is stopped and must be set
EEE
bAt
331
• Battery capacity is <85%
• Clock is stopped and must be set
• Operator confirmation required
• Message appears weekly after confir-
mation
• Battery should be replaced
EEE
bAt
332
• Battery capacity is <75%
• Clock is stopped and must be set
• Operator confirmation required
• Message appears daily after confirmation
• Battery should be replaced
Battery monitoring function
The device indicates the condition of the battery via
the "EEE" symbol followed by "bAt" and the status num-
ber. Depending on the status number a confirmation of
the information by the operator may be required. It is re-
commended that the battery be replaced.