P0-16
Carrier frequency
adjusted with
temperature
0: no 1: yes
1
☆
61456
P0-17
Acceleration time 1
0s
~
65000s ( P0-19 =0)
0.0s
~
6500.0s ( P0-19 = 1)
0.00s
~
650.00s (P0-19 =2)
Model
confirmed
☆
61457
P0-18
Deceleration time 1
61458
P0-19
Acceleration and
deceleration time unit
0: 1 second
1 : 0.1 second
2 : 0.01 second
1
★
61459
P0-21
Auxiliary frequency
source during
superposition
Bias frequency
0.00Hz
~
maximum
frequency P0-10
0.00Hz
☆
61461
P0-22
reserve
-
-
-
-
P0-23
Digital setting
frequency stop
memory
0: no memory 1: Memory
1
☆
61463
P0-24
reserve
-
1
☆
61464
P0-25
Acceleration and
deceleration time
base frequency
0: maximum frequency (P0-10)
1: set frequency
0
★
61465
P0-26
Frequency command
UP/DOWN reference
during operation
0: Running frequency
1: Setting frequency
0
★
61466
P0-27
command source
bundled frequency
source
Units: Operation panel
command binding frequency
source selection
0 : No binding
1 : Digital setting frequency
2 : AI1
3 : AI2
4 : AI3 external keyboard
potentiometer
5 : PLUSE pulse setting
(DI5)
6 : Multi-stage speed
7 : Simple PLC
8 : PID
9 : Tens digit of
communication reference
: terminal command binding
frequency source selection
Hundreds place:
communication command
binding frequency source
selection
Thousands place: automatic
operation binding frequency
source selection
0000
☆
61467
P0-2 9
application macro
Setting range : 0 ~ 65535
1000
0 : function code restore
factory default macro
0
☆
61469
6