3 : Run at the lower limit
frequency
4 : Run at the abnormal
standby frequency
P9-55
Abnormal standby
frequency
60.0%
~
100.0%
(100.0% corresponds to the
maximum frequency P0-10)
100.0%
☆
63799
P9-59
Instantaneous power
failure action
selection
0: Invalid
1 : Deceleration
2 : Deceleration to stop
0
☆
63803
P9-60
Momentary power
failure action pause
judgment voltage
P9-62
~
100.0%
100.0%
☆
63804
P9-61
Instantaneous power
failure voltage
recovery judgment
time
0.00s
~
100.00s
0.50s
☆
63805
P9-62
Instantaneous power
failure action
judgment voltage
60.0%
~
100.0%
(standard bus voltage)
80.0%
☆
63806
P9-63
Load Loss Protection
Selection
0: invalid
1 : valid
0
☆
63807
P9-64
Load drop detection
level
0.0
~
100.0%
10.0%
☆
63808
P9-65
Load drop detection
time
0.0
~
60.0s
1.0s
☆
63809
PA Group PID function
Function
code
Name
Setting range
Factory
default
Attrib
utes
DEC
address
PA-00
PID given source
0: PA-01 setting
1 : AI1
2 : AI2
3 : AI3 external keyboard
potentiometer
4 : PLUSE input pulse
setting (DI5)
5 : Communication setting
6 : Multi-segment command
setting
7 : Given by the pressure of
water supply group b0-01
0
☆
64000
PA-01
PID value given
0.0
~
100.0%
50.0%
☆
64001
PA-02
PID feedback source
0: AI1
1 : AI2
2 : AI3 external keyboard
potentiometer
3 : AI1-AI2
4 : PLUSE input pulse
setting (DI5)
5: Communication reference
6 : AI1+AI2
7 : MAX (|AI1|, |AI2|)
8 : MIN (|AI1|, |AI2|)
0
☆
64002
PA-03
PID action direction
0: Positive action 1: Reverse
action
0
☆
64003
6
Janson Controls Technologies(Shenzhen) Co.,Limited
Chapter6 Brief Introduction of Function Parameters
FC100P Series Manual V1.0
-49