22 

 

 

 

5.4 

 Auto-Restart

 

 

If the Input Power Cord is connected to the wall receptacle properly and 

Utility is back to normal, the UPS will automatically restart to provide energy to the 
output after battery cut.

 

 

5.5 

 Alarm Silence

 

 

1. 

The Alarm might be turned off by pressing the “On” Switch for 

approximately 1 second in the “Backup” mode. 

 
2. 

Unless any other warning or fault condition occurs, the alarm remains at 

Silence condition once the “Alarm Silence” is turned off. 

 

5.6 

 Self Test

 

 

1. 

Under Utility Normal condition, press the “On” Switch for 3 seconds to 

execute the Battery Self-test function. 

 
2. 

In case the battery is normal, it will enter into the Battery Backup Mode for 

10 seconds then return to Utility Mode. 

 
3. 

If the battery voltage is detected lower than set limit, the Battery 

Replacement 

LCD 

  will blink for 5 seconds then extinguish to stop self-

test procedure. And if battery is detected weak or dead, the Battery 
Replacement 

LCD 

  will steadily illuminate. 

 

 

Caution--- 

The UPS will remain at “NO” output, if the start-up operation is not 
proceeded properly even though the Input Power Cord is connected 
to the wall receptacle. 

 

 

Important Notice---

 

Plug the UPS onto the wall receptacle to charge the UPS for over 8 
hours after initial installation.

 

 

 

Storage --- 

Store at -15 to +30 °C (+5 to +86 °F), charge the UPS battery every six 
months.  
Store at +30 to +45 °C (+86 to +113 °F), charge the UPS battery every 
three months

 

23 

 

 

UPS MAINTENANCE 

 

6.1 

 Battery Replacement  

 

When the UPS is started up or a self-test is executed, the Battery 

Replacement LED might light up due to battery weak or battery dead. 
 
 

1. When the Battery-Replacement (RED) lights up, you may leave the UPS to 

be re-charged for at least 8 ~ 10 hours to see whether the RED LED will be 
extinguished after the Self-test function is executed again. 

 
2. In case the RED LED remains unchanged, you may unscrew the Easy 

Swappable Battery cover, replace a new battery then push the “On” Switch 
to disable the RED LED.    Please follow the steps 1-3 to replace the new 
battery. 

 

 

Caution--- 

The UPS will remain at “NO” output, if the start-up operation is not 
proceeded properly even though the Input Power Cord is connected 
to the wall receptacle. 

 

 

Caution--- 

The battery is heavy, pull the battery out onto flat, stable surface. 

 

 

Caution--- 

DO NOT DISCONNECT the batteries while the UPS is in the BACKUP 
mode.

 

 

Summary of Contents for 120V 1000VA

Page 1: ...anel 12 3 10 UPS Rear Panel 13 4 INSTALLATION 18 4 1 Connect Utility and Load 18 4 2 Connect Network Surge protection 19 4 3 Connect Computer Interface Port 19 4 4 REPO Switch 20 5 OPERATION 21 5 1 Turn on the UPS 21 5 2 Turn Off the UPS 21 5 3 Plug in Charge 21 5 4 Auto Restart 22 5 5 Alarm Silence 22 5 6 Self Test 22 6 UPS MAINTENANCE 23 6 1 Battery Replacement 23 6 2 How to Replace Battery 24 6...

Page 2: ...units up to 3KVA are supplied with input cables and output sockets as standard z Plug and play USB RS232 interface conveniently offers a plug and play USB or RS232 port for connecting with nowadays IT products 3 2 IMPORTANT SAFETY INSTRUCTION 2 1 An Important Notice 1 The UPS has its own internal energy source battery Should the battery be switched on when no AC power is available there could be v...

Page 3: ...f the output is not cut completely 18 SAVE THESE INSTRUCTIONS This Manual Contains Important Instructions that should be followed during Installation and Maintenance of the UPS 19 Symbol for ON Off is displayed and defined 20 Intended for installation in a temperature controlled indoor area free of conductive contaminants 21 Maximum ambient temperature 40 or 0 40 for ambient Operating 2 2 Storage ...

Page 4: ...e instructions below 1 Keep at least 20cm 8 inches clearance from the rear panel of the UPS from the wall or other obstructions 2 Do not block the air flow to the ventilation openings of the unit 3 Please ensure the installation site environmental conditions are in accordance with the UPS working specifications to avoid overheat and excessive moisture 4 Do not place the UPS in a dusty or corrosive...

Page 5: ...8 3 6 Tower Setup Stand alone unit 9 3 7 Rack Mount Setup Step1 Step2 ...

Page 6: ...10 Step3 Step4 Step5 11 3 8 UPS Front Panel ...

Page 7: ...or or Ground Fault 13 Overload 14 Load Battery Level 15 Load Battery Level Indication Control Button 13 3 10 UPS Rear Panel 1000 1500VA 120V Item Description 1 Data Line Connectors 2 Voltage Configuration Switch 3 USB Port 4 RS232 DB 9 Port 6 1 NEMA 5 15R Output Receptacles 7 Cooling Fan 8 12A Input Circuit Breaker 1000 model only 15A Input Circuit Breaker 1500 model only 9 NEMA 5 15P Input Power ...

Page 8: ...g Vents 8 30A Input Circuit Breaker 9 NEMA 5 20P Input Power Core 10 REPO 11 Intellislot Port 15 3000VA 120V Item Description 1 Data Line Connectors 2 Voltage Configuration Switch 3 USB Port 4 RS232 DB 9 Port 5 1 15A Output Circuit Breaker for 6 1 5 2 20A Output Circuit Breaker for 6 2 6 1 NEMA 5 15R Output Receptacles 6 2 NEMA 5 20R Output Receptacles 6 3 NEMA 5 30R Output Receptacles 7 Cooling V...

Page 9: ...0 C14 Input Socket 10 REPO 11 Intellislot Port 17 2200 3000VA 230V Item Description 1 Data Line Connectors 2 Voltage Configuration Switch 3 USB Port 4 RS232 DB 9 Port 5 1 10A Output Circuit Breaker for 6 1 5 2 10A Output Circuit Breaker for 6 2 6 1 IEC 320 C13 Output Receptacles 6 2 IEC 320 C13 Output Receptacles 6 3 IEC 320 C19 Output Receptacles 7 Cooling Vents 8 15A Input Circuit Breaker 2200 m...

Page 10: ...ndow Caution Do not connect a laser printer to the UPS outlets 19 4 2 Connect Network Surge protection Connect a 10 base T 100 base T network cable with the RJ 45 network surge protection IN jack on the rear of the UPS Connect from the OUT jack with network cabling to network equipment 4 3 Connect Computer Interface Port Connect the supplied interface cable RS 232 or USB Optional between the inter...

Page 11: ...ch The UPS starts operating and Battery Backup LED Amber lights up The cold start up procedure is completed and the loads are supplied by the UPS 4 The UPS will run under Backup mode and the buzzer alarms every 2 seconds in case of blackout or over under voltage On the contrary If Utility is back to normal and then the UPS will run under Utility mode and silence alarm 5 2 Turn Off the UPS 1 Press ...

Page 12: ...n though the Input Power Cord is connected to the wall receptacle Important Notice Plug the UPS onto the wall receptacle to charge the UPS for over 8 hours after initial installation Storage Store at 15 to 30 C 5 to 86 F charge the UPS battery every six months Store at 30 to 45 C 86 to 113 F charge the UPS battery every three months 23 6 UPS MAINTENANCE 6 1 Battery Replacement When the UPS is star...

Page 13: ...24 6 2 How to Replace Battery STEP 1 STEP 2 25 STEP 3 STEP 4 1000 1500VA ...

Page 14: ...a DB 9 9 pin female connector on the rear to allow UPS status communications with a computer running UPS software The connection provides serial communication On Battery and Low Battery signals Table 4 DB 9 pin assignment DB 9 Pin Assignment Description 1 Low Battery open collector 2 UPS TxD 3 UPS RxD 4 N C 5 Common 6 N C 7 Low Battery open emitter 8 Utility Fail open emitter 9 Utility Fail open c...

Page 15: ...h relay contact is 40Vdc 25mA 8 1 4 Installation Position Optional Slot 8 1 5 Flexible signal output for N C Normal Close or N O Normal Open contact by shorting pin1 2 or pin2 3 form JP1 5 8 1 6 The shutdown function will be enabled in 1 minute after blackout occurs if the pin1 2 of both CN1 and CN6 are shorted by cap Or the shutdown function can only be enabled by pin9 10 of CN3 if the pin2 3 of ...

Page 16: ... after 10 minutes Normal Mode 120 Shutdown UPS immediately 100 119 Continuous Overload Alarm till end of battery discharged 120 130 Shutdown after 10 seconds Battery Mode 130 Shutdown UPS immediately Battery Parameters Type Valve regulated nonspillable lead acid Quantity x Voltage x Rating 3x36x7 3x36x9 6x72x7 6x72x9 31 Backup Time Full Load 3 14 2 33 2 41 2 32 Half Load 10 31 8 18 8 40 8 14 Recha...

Page 17: ...0 109 Continuous Overload Alarm and power to the load 110 120 Shutdown after 10 minutes Normal Mode 120 Shutdown UPS immediately 100 119 Continuous Overload Alarm till end of battery discharged 120 130 Shutdown after 10 seconds Battery Mode 130 Shutdown UPS immediately Battery Parameters Type Valve regulated nonspillable lead acid Quantity x Voltage x Rating 2x24x7 3x36x7 3x36x9 6x72x7 6x72x9 Back...

Page 18: ...34 35 192321372001003 ...

Reviews: