Jason International, Inc. •
501.771.4477
Page 5 of 26
Customer Service : 800.255.5766
Copyright © 2014 Jason International, Inc.
INSTALLATION INSTRUCTIONS (cont.)
Figure 8
eleCTrICal
Electrical Power Supply: These instructions are written
assuming 60Hz, 120V power supply. Special notations are
also included for the Export versions of the control equip-
ment, and power supply.
WARNING: Verification of electrical requirements
MUST be made before installation. Refer to the equip-
ment labels for voltage and frequency requirements.
NOTE: The bath is designed for indoor use only. The elec-
trical equipment must not be exposed to direct or indirect
water or moisture contact. The electrical equipment must
also be protected from dust and other airborne debris be-
fore, during, and after installation.
1. Electrical Service: A licensed electrician must pro-
vide the “dedicated” electrical service protected by a
GFCI. The location of the GFCI must be at least five (5)
feet (152 cm) away from the inside surface of the bath,
accessible for regular testing. Use copper conductors
only.
DANGER — RISK OF ELECTRIC SHOCK: Connect
only to a circuit protected by a Ground Fault Circuit
Interrupter (GFCI). In the unlikely occurrence of a cur-
rent imbalance in the power conductors, the GFCI will
interrupt the power to the bath.
WARNING: The electrical service to the GFCI must
not be interrupted by any control device. Likewise, the
electrical service from the GFCI to the bath control
should be direct and not interrupted by a switch. Never
use a switch in conjunction with a control device.
This will VOID THE MANUFACTURER’S WARRANTY.
2. GROUNDING IS REQUIRED. The unit should be
installed by a qualified service representative and
properly grounded.
3. INSTALL SERVICE CONNECTION AT LEAST 6"
(15cm) ABOVE SUB FLOOR.
ALL LOCAL AND STATE ELECTRICAL AND
PLUMBING CODES MUST BE OBSERVED. Where
there are no local codes the National Electric Code
(NEC) and Uniform Plumbing Code (UPC) shall be ob-
served. It is the responsibility of the installer/owner to
determine specific code compliance prior to installation
of the product.
NOTE: In the Commonwealth of Massachusetts,
installation is to be done by a Massachusetts licensed
plumber.
25. Drain and overflow. Complete the installation of the
drain and overflow per the instructions included with
the drain and overflow.
26. Test bath controls. Before finishing the installation,
it is recommended that the bath controls be tested
without filling the bath with water to assure that all
electric connections are properly working.
Note: Refer to the Electrical section for correct
installation of electrical components.
Note: Refer to the Product Test Diagnostics in
the Operating, Features, and Controls section for
testing.
27.
It is recommended that the bath be water tested (filled
and operated), and the bath be inspected for leaks
Refer to the FILLING AND DRAINING Instructions
in the Features and Controls section of this owner’s
manual.
28. Seal the joint between the skirt bottom and the floor
with a silicone caulk. See Figure 8.