INSTALLATION INSTRUCTIONS (cont.)
Figure 9
Figure 9A
NOTE: The load neutral terminal is not
used. There should be no connection
to the load neutral terminal on the GFCI
circuit breaker. The green wire (GND-
GREEN) is the equipment ground and
should be connected to the neutral bus
found in the main breaker box.
a dedicated 240v 20A, 50 Hz, GFCI protected circuit and
the pump control must be plugged into another dedicated
240v, 20A, 50 Hz, GFCI protected circuit.
(See Figure
9)
6.
Signature Edition Control Box.
The MicroSilk generator
unit is shipped separate from the bath. Follow the
instructions for the
MicroSilk Pump Assembly Field
Installation
in the
INSTALLATION
section of this owner’s
manual (instructions are also packaged with the MicroSilk
unit packaging). The pump is prewired to the control box.
The control boxes have a 36” (91cm) cord with plug end.
The MicroSilk and pump control boxes are mounted on
a stand that is temporarily secured to the packing board
for shipping. These boxes must remain on the control
box bracket so that the two boxes can communicate
properly through their infrared communication feature.
During installation, the control box bracket and controls
must be positioned horizontally and located to permit
access for inspection and servicing. The MicroSilk pump’s
power cord will need to be plugged into the control box.
Connect the pump’s male J+J plug to the female J+J plug
of the control box’s load line. The MicroSilk and pump
junction box must be plugged into a dedicated 240v 20A,
50 or 60 Hz, GFCI protected circuit.
(See Figure 9A)
DANGER: Do not alter the factory installed wiring.
All building materials and wiring should be routed
away from the equipment or other heat-producing
components of the unit.
Standard/Premier
Edition
Control Box
Light
Control Mount
L2
L1
GROUND
DEDICATED
240V,50 or 60 Hz
GFCI PROTECTED
SERVICE
NOTE: USE THE ABOVE
DIAGRAM FOR 240V, 50Hz
OR 60Hz SYSTEMS.
Neutral - White Wire
Hot - Black Wire
Ground - Green Wire
Dedicated
120V, 60 Hz
GFCI Protected
Service
Neutral - White Wire
Hot - Black Wire
Ground - Green Wire
Signature
Edition
Control Box
Ground
L2
L1
Dedicated
240V, 50 or 60 Hz
GFCI Protected
Service
Light
Control Mount
L2-WHITE WITH
RED MARK
L1-BLACK
GND-GREEN
FROM HEATER
FROM CONTROL(S)
L2
240 V
L1
NO CONNECTION
(LOAD NEUTRAL)
BREAKER BOX
Note: The load neutral terminal is not used. There should be no connection to the load neutral
terminal on the GFCI circuit breaker. The green wire (GND-GREEN) is the equipment ground
and should be connected to the neutral bus found in the main breaker box.
BREAKER BOX CONNECTIONS