6
Installation
When installing follow the requirements be-
low.
The boiler should be installed upright on a
safe level support/surface. There are four ad-
justable legs supplied with the boiler.
It is recommended to fit the boiler with a flue
gas sensor. Flue gas temperature in the boiler
must be at least 150 °C at normal use. Tem-
perature can be raised by removing the lowest
turbulent plate.
Boiler flue swiveling joint rotates by 90° to
the left, back and right. When rotated to the
right, the joint is turned upside down and fas-
tening and rotation direction of the flue gas
extractor fan motor is changed. Correct rota-
tion direction is marked on the flue swivelling
joint with an arrow.
Boiler Room
Leave free space of at least 1000 m in front of
the filling and maintenance hatches of the
boiler, at least 600 mm over the cleanout
hatch, and 400 mm on one side of the boiler.
Combustion air required for the boiler is sup-
plied from outside and the duct or valve area
should be at least half as large as the stack
area.
An arrow on flue
swiveling joint marks
motor rotation direc-
tion.
To the left,
rotation direction
counter-
clockwise.
To the back,
rotation direction
counter-
clockwise.
To the right,
rotation direction
clockwise, flue
swiveling joint
turned upside
down.
To the back,
rotation direction
clockwise, flue
swiveling joint
turned upside
down.