Start-up 

Check that: 

 

The flue is open and there is no installa-
tion or other waste at its base. 

 

The boiler and the heating system are 
filled with water and circulation is work-
ing. 

 

Piping connections are tight. 

 

The system is under pressure. 

 

The safety relief valve is working, i.e. 
water runs from the drain line during 
valve testing. 

Use a small amount of firewood for the first 
burning to avoid bar splitting by boiling water 
that could soak in the ceramic fire bar. 

If the system is filled for the first time the air 
dissolved in water will penetrate into the sys-
tem but will be removed from the boiler water 
when the temperature exceeds 90 ºC. When 
used for the first time, the system should be 
deaerated.

 

Control Panel 

 

1.  Pressure gauge.

 Measures pressure in the 

boiler.

 

2.  Thermometer.

 Measures water tempera-

ture in the boiler.

 

3.

 

Pump thermostat 60-90 ºC.

 Activates 

the charging pump when the boiler water 
achieves the setpoint. The setpoint should 
be at least 85 ºC under normal operating 
conditions.

 

4.

 

Smoke exhauster thermostat 90 ºC.

 De-

activates the smoke exhauster if the boiler 
water achieves the setpoint of 90 ºC.

 

5.

 

Flue gas thermostat 0-150 ºC.

 Deacti-

vates the smoke exhauster when the flue 
gas temperature drops to the setpoint. 

 

6.

 

Power switch.

 The power switch of the 

smoke exhauster and the charging pump.

 

7.

 

Pump thermostat indicator lamp.

 On 

when the pump is on.

 

8.

 

Flue gas thermostat indicator lamp.

 On 

when the smoke exhauster is on.

 

9.

 

Temperature limiter.

 Deactivates the 

smoke exhauster and the charging pump if 
the boiler water temperature exceeds 
98 ºC. The limiter will not actuate unless 
the instrumentation is improperly used or 
until it fails. Acknowledgement is pro-
vided by opening the protective cap and 
pressing the limiter. Note that the boiler 
water should cool down before acknowl-
edgement. 

Summary of Contents for Econature40

Page 1: ...07 2011 SOLID FUEL BOILER INSTALLATION AND OPERATION MANUAL J SPI HEATING PROFESSIONAL www kaukora fi...

Page 2: ...t Connection Diagram 8 Boiler Operation and Maintenance 8 Fuel 8 Start up 9 Control Panel 9 Firewood burning 10 Combustion Air Control 11 Maintenance 12 Cleaning 13 Troubleshooting 13 The boiler water...

Page 3: ...ns at a temperature above 100 C when the temperature exceeds 280 C the resulting reaction causes heat re lease Secondary combustion the reaction between pyrolytic gases and oxygen begins at a temperat...

Page 4: ...ax temperature 110 C Min temperature 0 C Max pressure 3 0 bar Standard pressure 1 5 bar Proof test pressure 4 0 bar Power consumption 0 12 kW Voltage 230 V Frequency 50 Hz Body protection IP 2X Furnac...

Page 5: ...accumulator 10 R15 FH drain connection 11 R25 FH expansion connection 12 R15 FH flue gas sensor analyzer connec tion 13 Sensor panel 14 Flame monitor glass 15 Upper primary air adjusting damper 16 Low...

Page 6: ...extractor fan motor is changed Correct rota tion direction is marked on the flue swivelling joint with an arrow Boiler Room Leave free space of at least 1000 m in front of the filling and maintenance...

Page 7: ...r three maximum valves if necessary To confirm functionality at least two safety relief valves are recom mended to be used at all times each having the required blowoff capacity The blowoff line of th...

Page 8: ...ora tion and remove most of it through the stack as unburnt flue gases thus uselessly loosing part of energy and resulting in soot formation in the stack Firewood is considered dry when the moisture c...

Page 9: ...pera ture in the boiler 3 Pump thermostat 60 90 C Activates the charging pump when the boiler water achieves the setpoint The setpoint should be at least 85 C under normal operating conditions 4 Smoke...

Page 10: ...ard onto the bar so that the blocks touch the rear wall of the furnace Set the smoke exhauster thermostat to the setpoint which is about 90 C The set point is correct if the smoke exhauster stops when...

Page 11: ...and ratio for burning varies depending on the wood to be burnt Primary and secondary air is factory adjusted for birch firewood Upper primary air does not have to be ad justed under normal operating c...

Page 12: ...tains air oxygen The hot system pressure should be lower than 1 5 bar and the cold system pressure higher than 0 5 bar 1 5 bar safety relief The water volume varies as the tempera ture i e the higher...

Page 13: ...boiler water temperature does not rise to the desired level Ensure that the primary and secondary air ratio and access are correct Ensure that the firewood is dry If there is a cooling coil in the boi...

Page 14: ...that the thermostat indi cator lamp is on since the set value of the extractor thermostat is 90 C Check the set value of the flue gas ther mostat Check that the temperature limiter has not tripped For...

Page 15: ...170 C Reduced flue pressure Pump speed Pump speed Upper primary air 0 Lower primary air 0 Secondary air 0 Expansion tank pre pressure Signature Warranty The warranty is confirmed to be two years for t...

Page 16: ...dit agency Declared agency 0424 Inspecta EY inspection certificate for the development of RS 419 07 Testing has been conducted to EN 303 5 test agency SP Sveriges Tekniska Forskningsinstitut declared...

Reviews: