Jäspi VLK
Operating instructions
24
Adjusting the tank temperature
The tank temperature is adjusted using the
adjuster dial on the front panel of the device.
We recommend setting the temperature to
approx. 60°C.
Adjusting the water flow temper-
ature
Adjust the device flow temperature with the
adjuster dial.
When adjusting the flow of water coming out
of the device, first turn the thermostat to its
minimum setting (-) and open the closest tap,
turning it to full hot.
Measure the water temperature while turning
the thermostat knob up (+). When the hot wa-
ter temperature reaches 55-60 degrees, the
device will be correctly adjusted. Ensure that
the tank temperature is then at least 60 de-
grees.
Checking the relief valve
The relief valve is checked by turning the knob
on the relief valve counter-clockwise until you
hear two clicks. Also ensure that water comes
out of the safety device discharge pipe.