RS T4F Diesel Generator | G625RS
11
General checks
Multi-voltage Selection
IMPORTANT NOTE: Operation of
the rotary switch must only be
carried out with the generator in
stop mode and electrically isolated
to prevent personal injury and
damage to the equipment. Changes
to the alternator voltage must be
completed by a suitably trained and
competent person. Please refer to
the operator manual for detailed
instructions including breaker
protection settings.
۱
۲
۳
A
A
D
Fig 6
A
Voltage control rotary switch
1
480/277V Three Phase
2
208/120V Three Phase
3
240/120V Single Phase
D
Padlock
NOTICE: A padlock must be
installed to prevent accidental
rotation of the multi voltage switch
whilst the generator is running,
otherwise damage will be caused to
the alternator.
Checks after running
Ensure that the electrical load is switched off
before stopping the engine.
>
Check that battery isolator is in the ‘off’ position.
>
Fill the fuel and DEF tanks. Make sure that the
filler caps and the area round the filler
openings are clean to avoid contamination of
the fuel and DEF.
>
Make sure that all the engine access doors are
closed and secured.
>
Check the condition of the cooling system
antifreeze.
>
If necessary, prepare for the next start by
connecting the cold climate equipment.
Coolant should be topped up when the engine is
stopped. Make sure that enough time is allowed
for the engine/coolant to cool before the radiator
cap is removed.