CONTROL PANEL
–
DSE 8610
A Module display
B Four configurable status LED
C Close generator
D Generator available LED
E Start button
F Alarm mute and lamp test
G Auto mode
H Generator breaker LED
J Manual mode
K Stop/reset button
L Selected mode indication LED
M Open generator (manual mode only)
N Module display Menu navigation buttons
This button places the module into its STOP/RESET mode. This will clear any alarm conditions for which the
triggering criteria have been removed. If the engine is running and the module is put into STOP/RESET mode,
the module will automatically instruct the generator to unload ('Close Generator output' becomes inactive. In
STOP/RESET mode the generator remains at
rest.
This button places the module into its MANUAL mode. Once in MANUAL mode, the module responds to the
start button to start the generator and run it off load. To place the generator on load, use the 'Transfer to
Generator‘ button. The module automatically instructs the generator to synchronise and once in sync, to be
place the generator on load (‘Close Generator Output’ becomes active). To place the generator off load, use
the 'Open Generator‘ button. The module automatically ramps the load off the generator and then takes it off
load (‘Close Generator Output’ becomes inactive). Additional digital inputs are available to perform these
functions. If the generator is running off-load in MANUAL mode and on load signal becomes active, the module
automatically instructs the generator to synchronise and once in sync, to be place the generator on load (‘Close
Generator Output’ becomes active). Upon removal of the on load signal, the generator remains on load until
either selection of the 'STOP/RESET' mode or 'AUTO' mode.
This button places the module into its AUTO MODE. This mode allows the module to control the function of
the generator automatically. The module monitors numerous start requests via digital input, PLC and MSC link
and when one has been made, the set is automatically started. Once the generator is available, the module
automatically instructs the generator to synchronise and once in sync, to be place the generator on load (‘Close
Generator Output’ becomes active). Upon removal of the starting signal, the module starts the Return Delay
Timer and once expired, the load is automatically ramped off the generator and then it is taken off load (‘Close
Generator Output’ becomes inactive). The generator then continues to run for the duration of the Cooling
Timer until it stops. The module then waits for the next start event.