For Non-Vented (recirculating) Installations
If it is not possible to vent cooking fumes and vapors to the
outside, the hood can be used in the non-vented (recirculating)
version, fitting a charcoal filter and the deflector. Fumes and
vapors are recycled through the top grille.
NOTE:
Wall venting can be an option for 2-story homes.
Calculating Vent System Length
To calculate the length of the system you need, add the
equivalent feet (meters) for each vent piece used in the system.
Maximum equivalent vent length is 35 ft (10.7 m).
Example Vent System
The following example falls within the maximum vent length of
35 ft (10.7 m).
Electrical Requirements
Observe all governing codes and ordinances.
Ensure that the electrical installation is adequate and in
conformance with National Electrical Code, ANSI/NFPA 70 (latest
edition), or CSA Standards C22.1-94, Canadian Electrical Code,
Part 1 and C22.2 No. 0-M91 (latest edition) and all local codes
and ordinances.
If codes permit and a separate ground wire is used, it is
recommended that a qualified electrician determine that the
ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
CSA International
8501 East Pleasant Valley Road
Cleveland, OH 44131-5575
■
A 120 volt, 60 Hz., AC only, 15-amp, fused electrical circuit is
required.
■
If the house has aluminum wiring, follow the procedure
below:
1.
Connect a section of solid copper wire to the pigtail
leads.
2.
Connect the aluminum wiring to the added section of
copper wire using special connectors and/or tools
designed and UL listed for joining copper to aluminum.
Follow the electrical connector manufacturer's recommended
procedure. Aluminum/copper connection must conform with
local codes and industry accepted wiring practices.
■
Wire sizes and connections must conform with the rating of
the appliance as specified on the model/serial/rating plate.
The model/serial/rating plate is located behind the left filter
on the rear wall of the range hood.
■
Wire sizes must conform to the requirements of the National
Electrical Code, ANSI/NFPA 70 (latest edition), or CSA
Standards C22. 1-94, Canadian Electrical Code, Part 1 and
C22.2 No. 0-M91 (latest edition) and all local codes and
ordinances.
Roof venting
Non-vented (recirculating)
A. Roof cap
B. 6" (15.2 cm) round vent
A. Deflector
B. 6" (15.2 cm) round vent
Vent piece
6" (15.2 cm) round
45° elbow
2.5 ft
(0.8 m)
90° elbow
5.0 ft
(1.5 m)
1 - 90° elbow
= 5.0 ft (1.5 m)
1 - wall cap
= 0.0 ft (0.0 m)
8 ft (2.4 m) straight
= 8.0 ft (2.4 m)
System length
= 13 ft (3.9 m)
A
B
A
B
90 elbow
6 ft (1.8 m)
2 ft
(0.6 m)
Wall cap