Operating instructions
HMCflex
17/23
© ehb errors and omissions excepted
cool down time (Cdown).
disengage
Monitoring of the start speed can be programmed as powering down (shutd),
warning (alarm), without monitoring (without) or as power down with cool down
time (Cdown).
min.speed
Monitoring of under speed can be programmed as powering down (shutd),
warning (alarm), without monitoring (without) or as power down with cool down
time (Cdown).
overspeed
Monitoring of over speed can be programmed as powering down (shutd), warn-
ing (alarm), without monitoring (without) or as power down with cool down time
(Cdown).
diverse
Monitoring of the various input can be programmed as powering down (shutd),
warning (alarm), without monitoring (without) or as power down with cool down
time (Cdown).
[8] error delays
oil min
The setting gives the time period for how long an existing oil pressure error is
suppressed by the management system. After this time period expires, the
alarm event programmed under [7] comes into play.
temp. max
The setting gives the time period for how long an existing temperature error is
suppressed by the management system. After this time period expires, the
alarm event programmed under [7] comes into play.
D+
The setting gives the time period for how long an alternator charging error is
suppressed by the management system. After this time period expires, the
alarm event programmed under [7] comes into play.
various
The setting gives the time period for how long an existing signal on the various
input is suppressed by the management system. After this time period expires,
the alarm event programmed under [7] comes into play.
min.speed
The setting gives the time period for how long a below-level speed is sup-
pressed by the management system. After this time period expires, the alarm
event programmed under [7] comes into play.
max. speed
The setting gives the time period for how long an excess speed is suppressed
by the management system. After this time period expires, the alarm event
programmed under [7] comes into play.
[9] Limit values
temp. max
Setting of the limit value for the max. engine temperature. When the pro-
grammed temperature is exceeded, the alarm event programmed under [7]
comes into play.
boot speed
Setting the limit value for the start speed. If the start speed is not reached, the
alarm event programmed under [7] comes into play.
min.speed
Setting a lower engine speed. If the speed falls below this level, the alarm
event programmed under [7] comes into play.
max. speed
Setting an upper engine speed. If the speed exceeds this level, the alarm event
programmed under [7] comes into play.
Summary of Contents for 561305770
Page 2: ......
Page 4: ......
Page 6: ......
Page 8: ......
Page 10: ......
Page 12: ......
Page 14: ......
Page 54: ......
Page 56: ......
Page 58: ......
Page 60: ......
Page 82: ......
Page 84: ......
Page 87: ...Service Schedule...
Page 91: ...Original Ersatzteile Original spare parts Pi ces de rechange d origine...
Page 92: ...Hydraulikanlage Hydraulic system Circuit hydraulique...
Page 100: ...Einf hrtrichter klappbar Infeed chute Tremie d alimentation...