Operating Modes | Operating Manual GW 702 | 19
9. Operating Modes
Operating states of the measurement amplifier GW 702.
Power-up phase
The connected sensor can deliver undefined values to the measurement amplifier GWZ 702 directly after
the system has powered up. This situation can lead to false alarms. All alarm messages are therefore
blocked for approx. 20 seconds after power-up or after a voltage interruption with a start delay.
Data logging
The data logging of the measurement amplifier GW 702 takes place automatically. The status is not indi-
cated in the display. The measured values of the sensors are visible over the menu Service (see section 13).
Sensor test
The device automatically checks electronically the signal of the sensor. The time interval between two suc-
cessive tests can be specified in hours in the main menu under "Sensor Test". (see section 8.3)
Alarm
Two alarm thresholds can be set, Limit Value 1 and Limit Value 2. When the alarm thresholds are exceeded,
instead of the measured value display the display indicates "Erase Alarm, press key
".
With key
the alarm is acknowledged manually and the relay is switched.