36 | Maintenance Instructions TOPAX DX | BA-40100-0-V04
Chapter 16: Menu structure and configuration
Menu 2.3: recorder (Analog output 0/4-20 mA)
mg/l
mV
pH
039 702 719 09
0
ESC
free chlorine
pH value
REDOX
temperature
next
inputs
mg/l
recorder
2.3
main menu >> menu >> recorder
mg/l
mV
pH
039 702 719 09
0
ESC
comb. cl.
% salt
recorder
input
2.3
main menu >> menu >> recorder >> next >> page (at more than 5
inputs))
For the remote indication of the measured values, TOPAX DX has
a similar output for each measured value input 0/4... 0 mA.
Any measurement can be assigned to a minimum value or a
maximum value.
Menu
Input
Button
Required value
Unit
.3.1
free chlorine
free chlorine
min. / max
mg/l
.3.
pH value
pH value
min. / max
-
.3.3
Redox
Redox
min. / max
mV
.3.4
temperature
temperature
min. / max
ºC
.3.5
combinded chlorine
comb. cl
min. / max
mg/l
.3.6
salt content
% salt
min. / max
%
Select in input. Choose between „minimum“ or „maximum“ to
set upper and lower limit of the measured value.
Enter the requested value:
The first digit of the target value is highlighted in grey and can be
adjusted. Use the arrow keys to set up the value:
◀
/
▶
switch over between the individual positions
▲
/
▼
alter numerical values
„OK“
to save (press times)
Menu 2.4: night mode
mg/l
mV
pH
039 702 719 09
0
ESC
timer
off
night mode
on
setpoint
setup
AUS
2.4
mg/l
circulation
main menu >> menu >> night mode
Night-time operation mode
• can be set to switch manually on or off.
• the default for the „free chlorine“ controller has to be set.
• a percentage value can be further set for reduction of
recirculation power.
• Timer data input and selection are done in the menu 5.8
“timer”.