Adhere to the safety requirements in the table below when selecting the
fan location.
f.
The fan should be visible from the location of the wall controller. The
mounting structure must be able to withstand the torque forces
generated by the fan.
Safety Requirement Minimum Distances
Clearance
Minimum 250mm from all fan parts. The fan installation area
must be free of obstructions such as light, cables, sprinklers,
or other building structure.
Blade height
At least 3 meters above the floor
Fan spacing
4 x fan diameter, centre-to-centre, unless otherwise
specified by Jet Black Fans or client
Install Appendix
Mounting Details for Square Beam
Note:
Installer must cut the threaded rods to required length.
Mounting Details for Square Tube
Note
: If using this method, a Structural Engineer should be engaged to advise the
structural requirements for your building.