Fill-Settings menu
The "Fill-Settings" menu is used to set/specify the program parameters associated with the selected
model/filling program.
The settings made in this menu are all assigned to the selected (in the RUN menu) model (=filling
program)!
Parameter Name
Options/
Value Range
Description
Fuel tank type
"Standard tank"
"Bladder tank"
Defines the type of tank system to be filled.
"Standard tank"
=normal tank system of one or
more "hard" tanks.
The tanks can be connected in series or in parallel.
"Bladder tank"
=Bag tank of one or more bag tanks
connected in parallel.
Stop-Signal
"Flow/Pressure "
"2-line flowback"
Defines the shutdown signal to be used for "tank
full" detection.
Only available if "fuel tank type" is not set to
"bladder tank".
See also pages: 10-19 !
"Flow/Pressure" =switching off via pressure increase
"2-line flowback" =shutdown via fuel return flow in
the flowback line
Fill-PumpPower %
25-100% [80%]
Pump capacity during filling in %
Reasonable values are between 40 and 95%.
For bag tanks 80% is ideal.
Flow-Drop %
1-20%, [
3%]
Definition of flow drop in % for "tank full" detection.
Reasonable values are between 2 and 5%.
A set value of e.g. 3% means that for full tank
detection the flow rate must decrease by 3%
Values that are too high (e.g. 15%) can lead to high
pressure in the tank, values that are too low (e.g.
0.5%), to a possibly too early/premature shutdown.
AutoDecompress
0.0-2.0 ; [1.0]
Defines the scaling factor of the automatically
calculated drawback volume when filling bag tanks
(not available for other tank types).