Option 2: Bolting Mounting

  Each module should secure the frames of module to sup- 
   porting structure through at least 4 mounting holes (corres- 
  ponding to the mounting rail 2 and 3). For high wind and 
  snow loads, 8 holes (corresponding to the mounting rail 1 to
  4) should be secured. The module frame must be attached 
  to the mounting rails using M8 corrosion-proof screws
  together with spring washers and flat washers. Recommen- 
  ded torque is 5Nm. Use the exiting installation holes instead 
  of drilling additional holes for installation (Drilling holes is  
  against the reliability and warranty of Jetion modules). Please
  use corrosion-resistant installation and attachment materials. 

Fig. 5

 

Mounting rail 1

Mounting rail 2

Mounting rail 4

 

 

 

Mounting rail 3

8-[   9×14 

Nut

Mounting rail

M8 srew

960

1300

1300
1100
1044

1100

1225

1676

1195×541x30

1580×808x40

1580×1069x45

1482×676x40
1324×992x40

1482×992x40

1655×992x40

1956×992x45

660x508

800x758

800x1019

700x626
544x942

700x942

725x942

1176x942

JT***SFa/b

JT***SAa/b

JT***SAa/b(Black)

JT***SBa/b

JT***PFe/JT***SFc

JT***PEe/JT***SEc

JT***PDe/JT***SDc/

JT***SDc(Black)

JT***PCe/JT***SCc/

JT***SCc(Black)

JT***PAe/JT***SAc

Mono

Mono

Mono

Poly/Mono
Poly/Mono
Poly/Mono

Mono

Poly/Mono

Mono

Poly/Mono

4 x 9

6 x 12

8 x 12

4 x 9
6 x 8

6 x 9

6 x 10

6 x 12

Module Type                        Cell Type         Cell           Dimensions           Mounting Hole    Mounting Hole

   

                                

Quantity  

    

A x B x C (mm) 

       

 E

 

(mm)           G x F (mm) 

Table 5

Notes: 
1) JT***SFa/b is used as an example.
2) Where “***” is the rated power of the Jetion module.

4) Grounding

  To avoid the risk of electrical shock or fire, the module frame  

  should be grounded before the electrical connection of the  
  modules is operated.

  The frame shall be grounded in accordance with NEC Article  

  250[USA[or CEC in Canada.

  For an adequate ground, the grounding hardware should  

  penetrate the anodization layer.

  Only UL listed components should be used for grounding.

  Jetion recommends using the following components or equi- 

  valents.

1  Stainless steel bolt M4 x 30
2  Stainless steel nut M4
3  Stainless steel spring washer M4
4 & 6   Stainless steel flat washer M4
5  Stainless steel lock-toothed washer M4
7  Stainless steel cup washer M4
8  Grounding wire

Fig. 6

Washer

Summary of Contents for JTxxxSFb series

Page 1: ...Installation Manual Visionary green energy...

Page 2: ...enance Jetion reserves the right to update the product specifications or this Installation Manual without prior notice 1 Certificates requests 1 1 IEC 61730 Jetion modules are designed to fulfill the...

Page 3: ...other modules When a bypass diode is wired in parallel with the series string the forced current will flow through the diode and bypass the shaded module thereby minimizing module heating and array c...

Page 4: ...system The modules are Class C You can mount them over a Class C B or A roof The amount of area the modules cover may degrade the roof s original fire rating in some loca tions Do not install modules...

Page 5: ...2 12 12 12 0 5 2 0 5 2 0 5 2 0 5 2 0 5 2 0 5 2 0 5 2 0 5 2 2 5 3 2 5 3 2 5 3 2 5 3 2 5 3 2 5 3 2 5 3 2 5 3 M8 Screw Middle Modules Installation Frame long side Mounting rail Clamp The movement of the...

Page 6: ...2 725x942 1176x942 JT SFa b JT SAa b JT SAa b Black JT SBa b JT PFe JT SFc JT PEe JT SEc JT PDe JT SDc JT SDc Black JT PCe JT SCc JT SCc Black JT PAe JT SAc Mono Mono Mono Poly Mono Poly Mono Poly Mon...

Page 7: ...ons we recommend cleaning the modules using plenty of water from a hose with mild detergent and using a gentle cleaning implement a sponge CAUTION DON T USE DETERGENTS CONSISTING OF ABRASIVE ACETONE O...

Page 8: ...ically conducting parts into the plugs or sockets Do not fit solar modules and wiring with wet plugs and sockets Exercise utmost caution when carrying out work on wiring and safety equipment use insul...

Page 9: ...ww jetion biz JETION SOLAR CHINA Jetion Solar China Co Ltd No 1011 Zhencheng Road Shengang Jiangyin Municipality Jiangsu Province 214443 Peoples Republic of China Phone 86 510 8668 7300 Fax 86 510 866...

Reviews: