Page 7

1500 unit -

A minimum 720mm deep x 1600mm wide x 100mm thick non-combustible insulating floor protector (Hebel blocks) should be used
under the appliance, a minimum 1900mm wide x 900mm deep x 100mm overall thick non-combustible insulating floor protector
(Hebel blocks) must be used in front of the appliance base when installing the appliance (see joint AS/NZS 2918:2018 3.3.2).
The floor protector should extend 900mm in front of the appliance opening and be placed centrally in the 1900mm width.
100mm thick floor protector projection can consist of multi-layered non-combustible materials.

1200 unit -

A minimum 720mm deep x 1300mm wide x 100mm thick floor protector (Hebel blocks) should be used under the appliance, a
minimum 1650mm wide x 900mm deep x 100mm thick floor protector (Hebel blocks) must be used in front of the appliance base
when installing the appliance (see joint AS/NZS 2918:2018 3.3.2).
The floor protector should extend 900mm in front of the appliance opening and be placed centrally in the 1650mm width.
100mm thick floor protector projection can consist of multi-layered non-combustible materials.

The Thermal resistivity of the floor protector is 0.65m².K/W for 100mm thick Hebel Blocks. The Thermal resistivity for 75mm PowerPanel
is 0.59m².K/W

4. Clearance requirements

Non-combustible material up to outer
flange to 600mm above opening and
200mm to the sides.

If elevating unit above finished hearth
level, lower wall finishing must also be
non-combustible.

Hebel 600mm min.
above firebox.

50mm min. clearance to

combustibles within ceiling cavity

and penetration points

Timber framing at zero
clearance to 75mm hebel
power panel.

Ensure lower air intake is
not obstructed

50mm clearance to outer skin
of flue in all directions

Minimum 1650mm - 1200 unit
Minimum 1900mm - 1500 unit

200mm

Fig 3.4

Clearance to an adjacent wall for units 1500 & 1200 and should be 1200mm in all directions as per clause 3.2.2(b) 2918:2018

900mm

Summary of Contents for 1200 series

Page 1: ...only Other fuels may over fire and generate poisonous gases i e carbon monoxide Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance Do not...

Page 2: ...11 6 General use Attaching firescreen lighting a fire 12 6 General use Fuels Cleaning Maintenance Safety 12 AS NZS 2918 2018 General notes Thank you for purchasing a Jetmaster fireplace Please read th...

Page 3: ...is with height of chimney minimum 4 6 metres as per AS NZS 2918 2018 C Negative Pressure Negative pressure results from the imbalance of air available for the appliance to operate properly It can be...

Page 4: ...flow of outdoor air for all combustion appliances and exhaust equipment Ensure cental heating and air conditioning return vents are not located in the vicinity of the appliance Avoid installing the a...

Page 5: ...1500 dual spigot gather 1550 1600 600 1000 400 300 350 450 150 Measurements are in mm and provided as a reference only Double flue size is 50mm bigger than the above F measurements Dual spigot will r...

Page 6: ...plications an AGA approved cowl must be used C D Measurements are in mm and provided as a reference only Due to the nature of thick welded steel it is normal and expected for some imperfections and sl...

Page 7: ...GOT 1600 1730 750 1500 DOUBLE SPIGOT 1600 1730 690 Note Timber framing should be constructed using normal framing methods Image above is an example only Do not install finishing materials around the c...

Page 8: ...ce see joint AS NZS 2918 2018 3 3 2 The floor protector should extend 900mm in front of the appliance opening and be placed centrally in the 1650mm width 100mm thick floor protector projection can con...

Page 9: ...op of the appliance gather with 100mm R3 5 insulation compressed to 15mm between the appliance and Hebel PowerPanel Double spigot gather is narrower It is important to ensure Hebel cavity is within 15...

Page 10: ...ation cap away from trees adjacent structures uneven roof lines and other obstructions Your local dealer is the expert in your geographic area and can usually make suggestions or discover solutions th...

Page 11: ...crimp facing up to ensure water penetration on flue above roof runs out Rivet active flues together at crimped joins Fix outer non active flues to active inner flues use 3 x 25mm self tapping screws...

Page 12: ...side towards you with the steel handle provided 2 In firebox lay your fire lighters 10 to 15 centimetres apart depending on the size of your firebox Do not use newspaper as a fire lighter On units th...

Page 13: ...S NZS 2918 General notes Fuels The quality of firewood is extremely important How long a tree has been felled or dead for does not indicate how dry the wood is The best way to dry wood is to split it...

Reviews: