background image

Refer to the minimum framing dimensions as per table 2. Allow a temporary lintel height (see table 2 ‘B’) from the

finished floor protector level until the firebox and flue system is installed. Install front nogs on edge to increase chimney

chase dimension.

Ensure suitable air vents (2 x 80mm diameter or equivalent) in place to vent firebox space - these maybe located in the

floor or in the side wall space. Ensure vents must be bird and vermin proofed.

Note:

Wood Installations can be converted to Gas at a later date. or have a gas ignition system fitted. Consider running a

gas supply to firebox cavity at the time of construction.

FIREBOX INSTALLATION

1. All dimensions shown for the framing trim out and metal heat shields, are based on a maximum frontal clearance 

between the timber framing and the rear of the firebox fascia,

being not more than 15mm

.

2. Locate floor protector in trim out cavity. If on a concrete floor, suggest a mortar screed to the underside of the floor 

protector. If on a wooden floor, screw or dynabolt in place.

3. Locate stud openings on both sides.

4. Position and ensure a strip of glass rock wool insulation is between the inner hebel leg face and the firebox. Nail

through stud into hebel leg to secure in place.

5. Locate and position firebox, fit and seal gather in cavity (refer to Cross Section). Earthquake restraints may be

positioned by drilling through firebox into the floor protector, in a position midway beneath the log-pan. Two 12mm

dynabolts or similar will suffice. Do not over tighten and deform firebox.

6. Attach rock wool to the sides & back of the firebox and gather. DO NOT BLOCK OFF the air entry between the inner

flue pipe and flue pipe casing or the air circulation between the vent holes in the cavity.

7. Once the flue system is installed, place a minimum 300mm hebel block over the top of the firebox (see Fig. 8).

Ensure the hebel block does not rest on top of the firebox

. A Lintel Bar may be required.

TIMBER FRAMING PREPARATION

6.TMWG.6

FIREBOX INSTALLATION – GAS REQUIREMENTS

Please refer to the gas burner instructions supplied with the burner for full installation of the gas burner.

1 Before installing the fire box please drill a hole on the bottom right hand side of the fire box to allow for the gas pipe to 

be connected to the burner.

2. Location of the hole should align with the gap between the gas grate’s supporting legs.

3. The gas supply pipe enters the firebox above the base plate to terminate under the gas burner where it can be 

connected to the gas valve.

IMPORTANT : REMOVE THE DAMPER BLADE FROM THE FIREBOX

1. Unscrew the two friction bar adjustment nuts on the left hand side of the firebox and remove the friction bar.

2. To remove the Damper Blade, push the right hand side of the blade up and move the damper blade slightly to the

right to disengage the location bar on the left hand side of the damper blade, then slowly drop the blade down and

remove it.

IMPORTANT: GAS LEAKS

1. It is important to ensure that there are no gas leaks before commissioning the burner. It is the responsibility of the gas

installer to ensure that a leak testing method, suitable for the specific installation is being used.

2. Before commissioning, gas leaks can be detected only between the supply point and the inlet to the appliance. Once

the appliance is operational, an additional check must be done for leaks inside the appliance.

NOTE: GAS INSTALLATIONS

CAN NOT

BE 

CONVERTED TO WOOD BURNING AT A LATER DATE

Summary of Contents for 700

Page 1: ...warranty Due to continued product improvement The Fireplace Ltd reserves the right to change product specifications without prior notification Please check to ensure you have the latest installation...

Page 2: ...hield Firebox Installation Gas Requirements Plan Section Drawing Plan Section Recessed Drawing Masonry Cavity Dimensions Solid Fuel Flue Installation Gas Flue Installation Flue Penetration Chimney Cha...

Page 3: ...IN HEATER INSTALLATION CLEARANCES WHEN OPERATING THIS APPLIANCE AS AN OPEN FIRE USE A FIRE SCREEN THIS APPLIANCE SHOULD BE MAINTAINED AND OPERATED AT ALL TIMES IN ACCORDANCE WITH THESE INSTRUCTIONS US...

Page 4: ...ather available 1050IGC Box is ONLY for gas installations MODEL A A1 A2 B C D E F Y Off set Gather Indoor Gas Burner 700 700 800 750 400 700 225 325 200 680 295 395 Yes 850 850 950 900 450 700 250 350...

Page 5: ...ensure allowance is made to place non combustible internal wall lining eg Promatect H to cover the extent of the Hebel panel surround shown shaded Directly touching the firebox with any board or plas...

Page 6: ...r entry between the inner flue pipe and flue pipe casing or the air circulation between the vent holes in the cavity 7 Once the flue system is installed place a minimum 300mm hebel block over the top...

Page 7: ...ns must be bird rodent proofed with permanently fixed screens Gib Board Hebel Block Non combustible material eg Promatect H Lintel Bar Rock Wool insulation see Table 2 Secure the firebox with 2 x 12mm...

Page 8: ...x with 2 x12mm dynabolts for earthquake retraints Maintain the air intake unobstructed Floor Protector Fig 10 Fig 11 B see Table 2 Note All external air vents ceiling penetrations must be bird rodent...

Page 9: ...Floor Protector dimension RECESS REQUIRED 40mm Min 100mm Max Allow gas line into firebox if applicable Air Vent Y Refer toTable 2 for Floor Protector dimension Air Vent min 2 x 100 x 50mm or 80mm diam...

Page 10: ...side wall space make allowance min 2 x 80mm diameter or equivalent at the top of the chimney chase Pg 14 Ensure vents are bird and vermin proofed CROSS SECTION CAVITY PREPARATION 6 TMWG 10 Drawing No...

Page 11: ...pipe to be connected to the burner 2 Location of the hole should align with the gap between the gas grate s supporting legs 3 The gas supply pipe enters the firebox above the base plate to terminate u...

Page 12: ...ver spigot when fitted sizing measuring and cutting down should be carried out prior to the flue pipe casing being fitted over the flue pipe 2 Before fitting casing cover place the spider in oppositio...

Page 13: ...out prior to the flue pipe casing being fitted over the flue pipe 7 Before fitting casing cover place the spider in opposition with the spider post facing down between the flue pipe and flue pipe casi...

Page 14: ...r rectangle shaped area min 25mm gap between flue pipe casing combustible surface EXTERNAL REQUIREMENTS SOLID FUEL Refer to AS NZS2918 2001 4 9 1 Note All external air vents ceiling penetrations must...

Page 15: ...75 850 250 350 400 400 1050 IGC 250 300 350 350 1050 300 400 450 450 1200 400 500 550 550 1500 450 550 600 600 Table 4 CHIMNEY CHASE MINIMUM TRIM OUT 6 TMWG 15 MODEL A B C GAS B 700 1100 400 75 8 300...

Page 16: ...fer below for air vent sizing and suggested location Fig 26 Location points A B C D are suggested combinations A minimum of one pair of air vents is recommended or one large vent as per location point...

Page 17: ...tructed of combustible material it must be located within the shaded area defined in Fig 28 Fig 28 Projection mm Combustible Materials Non Combustible Materials CLEARANCE TO COMBUSTIBLE MANTELS 6 TMWG...

Reviews: