Jetter AG
Programming | 7
JCM-501-E00 User Manual
39 / 59
Variable ID
Variable type
FS
Flag
RS
Integer register
QA
Floating-point registers
Example
SD1001
; Data File - Jetter AG
;
; Registers 1000000 ... 1000005
RS 1000000 12345
RS 1000001 2
RS 1000002 -1062729008
RS 1000003 502
RS 1000004 50
RS 1000005 3
QS 1009000 3.14
;
; Flags 10 ... 13
FS 10 0
FS 11 1
FS 12 1
FS 13 0
Automatically load-
ing data file infor-
mation
The JCM-501-E00 has a mechanism that allows a data file to be loaded automat-
ically before the application program starts. You must name the data file
regis-
ter.da
and store it in the
App
folder.
Workflow
The table below shows how the device retrieves data file information:
Level
Description
1
If the data file
register.da
has been stored to the directory
App
,
the device will detect this file the next time the device is started.
2
The device retrieves the file.
3
The device maps the values to the registers.
4
Once the device has retrieved the file, it deletes the data file.
5
The device loads the application program.
7.12 Operating system update
Jetter AG are continuously striving to enhance the operating systems of their
products. Enhancing means adding new features, upgrading existing functions
and fixing bugs. Current OS files are available for download on our homepage in
the
Downloads
area of the respective product.
More information on this subject is available on our website.
Start | Jetter - We automate your success.
Transfer options
There are several options to transfer the OS file to the device:
■
With the programming tool JetSym
■
Via FTP connection
■
From a USB flash drive
■
Via device website
■
Via JetEasyDownload
■
Via directory
\App