JX2-PRN1
3 Operating Parameters
Jetter AG
15
Operating Parameters (EMC) - Immunity to
Interference of Signal Ports
Parameter
Value
Reference
Asymmetric RF,
amplitude-modulated
Frequency band 0.15 -80 MHz
Test voltage 10 V
AM 80 % with 1 kHz
Source impedance 150 Ohm
Criterion A
DIN EN 61000-6-2
DIN EN 61000-4-6
Burst
Test voltage 1 kV
tr/tn 5/50 ns
Repetition rate 5 kHz
Criterion A
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-4
Operating Parameters (EMC) - Immunity to
Interference of DC Power Supply In- and Outputs
Parameter
Value
Reference
Asymmetric RF,
amplitude-modulated
Frequency band 0.15 -80 MHz
Test voltage 10 V
AM 80 % with 1 kHz
Source impedance 150 Ohm
Criterion A
DIN EN 61000-6-2
DIN EN 61000-4-6
Burst
Test voltage 2 kV
tr/tn 5/50 ns
Repetition rate 5 kHz
Criterion A
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-4