5 Mounting and installation of the JVM-507B
Setting the IP address during runtime
The IP interface is initialized by the settings in the configuration memory
during the boot process.
The following volatile settings can also be changed via registers:
IP address
Subnet mask
IP address of default gateway
The settings made during runtime do not overwrite the parameters in the
configuration memory. At de-energizing the device, your settings will be lost.
Register
Description
104531
IP address of the HMI
104532
Subnet mask
104533
IP address of default gateway
To set the IP address and the subnet mask, proceed as follows:
Step
Action
1
Enter the desired IP address into R 104531.
2
Enter the desired subnet mask into R 104532.
3
Enter the desired IP address of the default gateway into R 104533.
Result:
The settings are completed. Communication is possible again.
The configuration memory
(see page 46)
Introduction
Important note
Registers - Overview
Setting IP addresses and
subnet mask
Related topics