Fieldbus/Modbus Communication Cabling
The controller is able to communicate using Modbus RTU (RS485) to JetVent Fans, Vacon Variable Speed Drives (VSDs), and
fieldbus sensors.
§
Devices must be connected in a daisy chain with the controller at the start of the chain. No star connections are
allowed, and if a branch is required a Modbus repeater must be used.
IMPROPER WIRING CONFIGURATION
END OF LINE X3
END OF LINE X8
§
Maximum communication wiring length is 500m before a Modbus repeater is required.
§
Separate conduit should be used for power and communications cable. Keep communications cable away from
devices that generate EMC interference, such as powered antennas, transformers, contactors, and neon lights.
§
Low capacitance (<100 pF/m) twisted pair cable with shield and an impedance of approximately 120 ohms/m @
100 kHz.
o
BELDEN 8761 (AWG22) is recommended for lengths under 500m
o
BELDEN 8762 (AWG20) is recommended for lengths over 500m