background image

Boilers / Hot Water Heaters / Furnace Common Drain

Flue Drain

Common Flue Vent

NBT pH Treatment Tanks

House Drain

Boilers / Hot Water Heaters / Furnaces

G    

Condensate Trap

Note: 

Contact Factory for pH Treatment Tank Piping Size

NBT

series Acidic Condensate pH Treatment Kits –– Installation/Operation & Maintenance

 

Inspect frequently

Installer — Instruct the building owner to 

frequently inspect the NBT tanks neutral-

izer and all condensate connections. The 

owner must notify a qualified technician 

if any problems are noticed.

Recharge as required

When pH tank outlet falls below 5PH. Lo-

cal codes may have different requirement, 

check with local authority. 
At least at a minimum once a year.

Cleaning

The baffle at the bottom of the NBT tanks 

should be lifted out every three years dur-

ing re-charging for cleaning of the tank 

bottom. This should be done by a trained 

technician.
Contact your local wholesaler or manu-

facturer’s representative for replacement 

parts. 
Dealer listing at www.jjmboilerworks.com

Maintenance

Environmentally Friendly

The pH Power Pellets® (Magnesium Hydroxide) pellets are NON-Hazardous to the 

environment and can be disposed of as normal refuge.  Do not allow children or ani-

mals to consume pH power pellets as they are not meant as a neutralizer for human or 

animal consumption.

Important

Remove porous pellet bag from plastic shippig bag before placing in the NBT tanks.

MSDS and SDS sheets are included with the NBT tanks or can be found on the JJM Boiler Works, Inc. website @ www.jjmboilerworks.com

8

Summary of Contents for NBT Series

Page 1: ...ion Maintenance Models NBT 610 NBT 230 14 Coleman Ave Westfield MA 01085 413 527 1893 690 Island Way Unit 206 Clearwater FL 33767 413 427 3373 jjmboilerworks com Revised August 2018 Acidic Waste Water...

Page 2: ...sedbythefollowing A Improper Combustion B Contaminated Combustion Air C High Sulfur Content in Gas Supply D pH below 2 0 is considered hazardous waste by EPA Contact JJM Technical Service at 413 427 3...

Page 3: ...BT 230 outlet level falls below 5 0 At a minimum the media bags must be changed once a year Use only JJM pH Power Pellet media bags DO NOTE USE LIMESTONE OR MARBLE CHIPS What is pH The pH measurement...

Page 4: ...ing Operational Flow 1 Once the heating unit is fired and acidic condensate is produced the condensate will flow from the heater condensate drain down into the NBT tank s inlet port The acidic condens...

Page 5: ...Boiler Works Inc 4 3 4 A B C D 7 8 3 5 INLET 7 8 From Base to Center 4D Outlet 3 1 2 Base to Center A E 6 50 E 1 NBT 610 pH Treatment Tank Part No 2010 NBT 23 pH Treatment Tank Ratings Dimensions in i...

Page 6: ...nt Tank Single Unit Condensate Pump igure 3 Key A Rev 01 2016 NBT 23 pH Treatment Tank B C D E F Boilers Hot Water Heaters Furnaces Condensate Drains Trap Flue Pipe Trap Floor Drain Note Contact Facto...

Page 7: ...d Piping Sizing D G Gas Water Trap G G C F F F F B E Piping Multiple Heating Units Single NBT 23 pH Treatment Kit Common Vent Piping Common Condensate Drain Figure 5 Key A Flue Drain B C D E Boilers H...

Page 8: ...nd install electric heat tape provide and install electric heat tape and insula tion on the condensate drain lines and around the NBT tanks to prevent possibility of neutralizer tube damage or line bl...

Page 9: ...rs dur ing re charging for cleaning of the tank bottom This should be done by a trained technician Contact your local wholesaler or manu facturer s representative for replacement parts Dealerlistingat...

Page 10: ...your neutralizer pellets are incased in a porous pellet bag there are three methods to agitating the pellets 1 Remove the pellet bag or bags from the tank and using your hands move the pellets around...

Reviews: