* 3-Wire is available.
10/9/03
IMPORTANT:
3-phase (3ø) figures shown are for a 3-wire service only.
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT
:
NOTES
: A.
B.
C.
208 VAC AND 230/240 VAC
ARE NOT THE SAME. When ordering,
specify
exact voltage
.
When fuses are used they
must be
dual element, time delay, current
limiting, class RK1 or RK5
ONLY
. Calculate/determine correct fuse
value, by applying either local and/or National Electrical Codes to
listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type
ONLY
. For
others, calculate/verify correct breaker size according to appliance amp
draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers
must be
3-pole type.
15 kW ELECTRIC
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
CIRCUIT
BREAKER
60 Hz
50 Hz
208
1ø
2
77
–
100
230/240
1ø
2
67
68
90
380
3ø
4*
–
28
35
20 kW ELECTRIC
208
1ø
2
101
–
125
230/240
1ø
2
88
89
125
380
3ø
4*
–
36
45
24 kW ELECTRIC
208
3ø
3
72
–
90
230/240
3ø
3
63
63
80
416
3ø
4*
–
39
50
460
3ø
3
32
–
50
b. Electric Models Only
ALL
electrically heated dryers
must
be
connected to the electric service shown on the dryer’s data
label. The connecting wires
must be
properly sized to handle the rated current.