48
TEMPERATURES MENU (CONT)
DESCRIPTION/ACTION
DISPLAY
•
Differential
- Adjustable user setting that changes the
tank temperature differential with a range of 2° to 20°F. The
factory setting is 8°F.
•
Tank Temperature
- non adjustable - control system
sensed temperature (averaged from upper and lower
temperature probes).
•
Upper Temperature
- non adjustable - control system
sensed temperature from the Upper Temperature Probe.
•
Lower Temperature
- non adjustable - control system
sensed temperature from the Lower Temperature Probe.
•
Tank Probe Offset
- adjustable user setting, range -5° to
+5° (factory setting 0°).
NOTE:
These settings should only be used if the hot water
supply temperature varies greatly from the Operating Set
Point setting.
The Tank Probe Offset is used to calibrate control system
temperature sensing. This can improve the precision of
temperature control in the storage tank and at points of use.
This feature can also be used to compensate for building
recirculation loops (hot water returning to the storage tank)
that may cause the heating cycles to terminate prematurely.
Example: If the current sensed temperature from a
temperature probe is 120°F (49°C) and the Offset setting is
adjusted to a value other than 0°, the control system would
calibrate or “offset” the sensed temperature from the probe
and the averaged tank temperature. Heating cycles would
be activated and deactivated based on the calibrated (offset)
temperature. A -5° setting results in +5° hotter water.
These settings are adjusted in the same way described for
Operating Set Point And Differential Adjustment on page 47.
Operating Set Point
140°F
Differential
8°F
Tank Temperature
120°F
Upper Temperature
122°F
Lower Temperature
118°F
Tank Probe Offset
0°F
CHANGE
BACK
HELP
Temperatures
HEATER STATUS MENU
DESCRIPTION/ACTION
DISPLAY
Select Heater Status from the Main Menu and press the
Operational Button under "SELECT" to enter this menu. This
menu contains non adjustable operational information. Use the
Up & Down Buttons to navigate the menu.
•
Status
- displays the current Operating State, see Table 15
on page 46.
•
ECO Contact
,
Low Gas PS
,
Blocked Inlet PS
,
Blocked
Outlet PS
,
Blower Prover PS
- displays the current state
of the switch contacts; open or closed.
•
Igniter On
,
Gas Valve On
- displays whether or not the
control system is currently energizing these water heater
components; yes = energized, no = de-energized.
•
Flame Detected
- displays whether or not the control
system has detected Main Burner flame during ignition from
the flame sensor.
Top of Menu
Status
Standby
ECO Contact
Closed
Low Gas PS
Closed
Blocked Inlet PS
Closed
Blocked Outlet PS
Closed
Blower Prover PS
Open
Igniter On
No
BACK
HELP
Heater Status
Bottom of Menu
Gas Valve On
No
Flame Detected
No
BACK
HELP
Heater Status