background image

IOM3723 Input/Output Module Installation Guide

Application

The MS-IOM3723 input/output expansion module

is a part of the Metasys system Field Equipment

Controller family. Input/Output expansion modules

(IOMs) expand the number of input/output points

connected to a General Purpose Application

Controller (CGM), VAV Box Controller (CVM), SNC,

SNE, Network Automation Engine (NAE), Network

Control Engine (NCE), Advanced Application Field

Equipment Controller (FAC), Field Equipment

Controller (FEC), or Variable Air Volume Modular

Assembly (VMA) to monitor and control a wide

variety of HVAC equipment.

Note: 

The IOM3723 model is only available

in certain regions. Contact your local Johnson

Controls representative for more information.

IOM expansion modules operate on an RS-485

BACnet

®

 MS/TP Bus and integrate into Johnson

Controls

®

 and third-party BACnet systems. IOMs

Note: 

With Release 10.1 of the Controller

Configuration Tool (CCT), VMAs, FECs, and

FACs can be configured to communicate using

either the BACnet MS/TP or the N2 field bus

networking protocol. The operation of the

IOM is not affected by the selection of the

BACnet MS/TP or the N2 protocol in the host

controller, when the IOM is connected to the

host controller using the SA bus.

North American emissions
compliance

United States

This equipment has been tested and found to

comply with the limits for a Class A digital device

pursuant to Part 15 of the FCC Rules. These limits

are designed to provide reasonable protection

against harmful interference when this equipment

is operated in a commercial environment. This

equipment generates, uses, and can radiate radio

frequency energy and, if not installed and used in

accordance with the instruction manual, may cause

harmful interference to radio communications.

Operation of this equipment in a residential area

may cause harmful interference, in which case the

users will be required to correct the interference at

their own expense.

Canada

This Class (A) digital apparatus meets all the

requirements of the Canadian Interference-Causing

Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte

toutes les exigences du Règlement sur le matériel

brouilleur du Canada.

Installation

Observe the following guidelines when installing an

expansion module:

• To minimize vibration and shock damage,

transport the expansion module in the original

container.

• Verify that all parts shipped with the expansion

module.

• Do not drop the expansion module or subject it

to physical shock.

Parts included

• One expansion module with removable

terminal blocks (Power and SA/FC bus are

removable)

• One installation instructions sheet

Materials and special tools needed

• Three fasteners appropriate for the mounting

surface (M4 screws or #8 screws)

• One 20 cm (8 in.) or longer piece of 35 mm

DIN rail and appropriate hardware for DIN rail

mount

• Small straight-blade screwdriver for securing

wires in the terminal blocks

Physical features

The following figure displays the physical features

of an IOM, and the accompanying table provides a

*24101431124E*

Part No.  24-10143-1124 Rev. E

2020-10-30

(barcode for factory use only)

MS-IOM3723

Summary of Contents for 24-10143-1124

Page 1: ...able protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and u...

Page 2: ...Termination Switch see Setting the End of Line EOL switch 6 Binary Input BI Terminal Block see Input and Output wiring guidelines 7 LED Status Indicators see Table 7 8 Mounting Clips Mounting Observe...

Page 3: ...ounting features and dimensions See the following figure for mounting dimensions listed in millimeters and inches Inches are listed in parenthesis The following figure also illustrates the DIN rail ch...

Page 4: ...n avant de r aliser un branchement lectrique Plusieurs isolations et d branchements sont peut tre n cessaires pour couper enti rement l alimentation de l quipement Tout contact avec des composants con...

Page 5: ...owing figure Figure 4 FC bus terminal block wiring When connecting the IOM to an SA bus wire the bus terminal block plugs on the expansion module and other SA bus devices in a daisy chain configuratio...

Page 6: ...idelines about the functions ratings and requirements for the expansion module input and output terminals and references guidelines for determining proper wire sizes and cable lengths In addition to t...

Page 7: ...pe Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 0 6 mm 22 AWG stranded copper 183 m 600 f...

Page 8: ...functions ratings requirements and cables Terminal block Port label Terminal labels Function electrical ratings Requirements Recommended cable type FC or SA Bus Communications COM Signal Reference Com...

Page 9: ...Device addresses 4 through 127 are the valid addresses for these expansion modules The DIP switch block has eight switches numbered 128 64 32 16 8 4 2 and 1 Switches 64 through 1 are device address sw...

Page 10: ...on module components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the expansion module Important Disconnect all power sources to the expansi...

Page 11: ...firmware package files refer to the CCT Installation Instructions LIT 12011259 LED status and states Observe the Status LEDs on the front of the expansion module Table 7 provides LED status indicator...

Page 12: ...and Y69 Transformers Product Bulletin LIT 125755 for more information AS CBLTSTAT Cable adapter for connection to 8 pin TE 6700 Series sensors AS XFR050 0 Power transformer Class 2 24 VAC 50 VA maximu...

Page 13: ...SA FC Bus and Supply Power 4 Wire and 3 Wire Pluggable Screw Terminal Blocks Mounting Horizontal on single 35 mm DIN rail mount preferred or screw mount on flat surface with three integral mounting c...

Page 14: ...other terms set forth at www johnsoncontrols com techterms Your use of this product constitutes an agreement to such terms Patents Patents https jcipat com Single point of contact APAC Europe NA SA JO...