Table 10: Menu navigation
Menu
Submenu
Parameters displayed
Conditions for parameter
displayed units and range
Heating status
Off-idle, SAT tempering, morning warmup,
thermostat heating, unoccupied heating, occupied
heating, Off-disabled, Off-OAT lockout, Off-SAT
limit, Off-waiting for changeover delay, comfort
ventilation
Air proving switch
Off, on
Supply fan %S command
%
Supply fan status
Off-idle, on-purge, on-gas valve or limit fault, on-
defrost
Modulating heat output
% / 0–100
Heat stage 1 status
Off, on
Heat stage 2 status
Off, on
Heat stage 3 status
Off, on
Heat stage 4 status
Off, on
Heat stage 5 status
Off, on
Heat stage 6 status
Off, on
Heat stage 7 status
Off, on
Heat stage 8 status
Off, on
Heat stage 9 status
Off, on
Heat
Heating status
Heat stage 10 status
Off, on
Heating mode enabled for operation
No, yes
Number of heating stages installed
0–10
Heating control type
None, gas, electric, hot water, steam
Occupied heating setpoint
°F / 40–85
Unoccupied heating setpoint
°F / 45–98
Discharge air temp setpoint configuration
Fixed, OAT reset, supply fan reset, zone temp
reset, external
Heating discharge air temp upper setpoint
°F / 86–135
Heating discharge air temp lower setpoint
°F / 85–134
Outside air temperature reset setpoint upper
°F / 61–131
Outside Air Temperature Reset Setpoint Lower
°F / 60–130
Zone temperature reset setpoint upper
°F / 61–131
Zone temperature reset setpoint lower
°F / 60–130
Supply fan discharge air temp setpoint high
threshold
% / 0–100
Supply fan discharge air temp setpoint low
threshold
% / 0–100
Heating adaptive tuning enable
No, Yes
Outside air temp heating cutout setpoint
°F / 0–100
Morning warmup enabled
No, Yes
Morning warmup/return air temp setpoint
°F / 50–85
Morning warmup discharge air temp setpoint
°F / 85–135
Unoccupied heating enabled
No, Yes
Discharge air temp tempering enable
No, Yes
Heating setup
Discharge air temp tempering setpoint
°F / 40–60
Staged heating command
%
Heat
Click >> to
continue to the
next page of
parameters
Heating Status
Off-idle, on-defrost, SAT tempering, morning
warmup, thermostat heating, unoccupied heating,
occupied heating, Off-disabled, Off-OAT lockout,
Off-SAT limit, Off-waiting for changeover delay,
comfort ventilation
Advanced Graphic Touchscreen Display on 25 Ton to 80 Ton Johnson Controls Premier Rooftop Units
31