Table 10: Menu navigation
Menu
Submenu
Parameters displayed
Conditions for parameter
displayed units and range
Operating heating setpoint
°F
Operating heating discharge air temp setpoint
°F
Operational outside air temperature
°F
Operational zone temperature
°F
Return air temperature
°F
Discharge air temperature
°F
Heating entering temperature
°F
Heat entering temp sensor alarm
Normal, alarm
Discharge air temperature tempering state
Disable, enable
Cooling status
Off-idle, thermostat cooling, unoccupied cooling,
occupied cooling, off-OAT lockout, off-disabled,
off-lockout, off-low supply voltage, off-low
ambient, off-low ambient pre-run delay, off-
waiting for changeover delay, off-free cooling,
comfort ventilation
Air proving switch
Off, on
Supply fan %s command
%
Supply fan status
(Off-idle, on-purge, on-gas valve or limit fault, on-
defrost)
Compressor 1A status
Off-idle, on-minimum on time, on-normal
command, off-cooling is disabled, off-OATcutoff,
off-low ambient temperature, off-low supply
voltage, off-high pressure lockout,off-low pressure
lockot, off freeze condition,off-anti short cycle
delay, off-cooling stage is disabled
Compressor 1B status
Off-idle, on-minimum on time, on-normal
command, off-cooling is disabled, off-OATcutoff,
off-low ambient temperature, off-low supply
voltage, off-high pressure lockout,off-low pressure
lockot, off freeze condition,off-anti short cycle
delay, off-cooling stage is disabled
Compressor 1C status
Off-idle, on-minimum on time, on-normal
command, off-cooling is disabled, off-OAT
cutoff, off-low ambient temperature, off-low
supply voltage, off-high pressure lockout, off-low
pressure lockout, off freeze condition, off-anti
short cycle delay, off-cooling stage is disabled
Compressor 2A Status
Off-idle, on-minimum on time, on-normal
command, off-cooling is disabled, off-OAT
cutoff, off-low ambient temperature, off-low
supply voltage, off-high pressure lockout, off-low
pressure lockout, off freeze condition, off-anti
short cycle delay, off-cooling stage is disabled
Compressor 2B Status
Off-idle, on-minimum on time, on-normal
command, off-cooling is disabled, off-OAT
cutoff, off-low ambient temperature, off-low
supply voltage, off-high pressure lockout, off-low
pressure lockout, off freeze condition, off-anti
short cycle delay, off-cooling stage is disabled
Cool
Cooling status
Compressor 2C Status
Off-idle, on-minimum on time, on-normal
command, off-cooling is disabled, off-OAT
cutoff, off-low ambient temperature, off-low
supply voltage, off-high pressure lockout, off-low
pressure lockout, off freeze condition, off-anti
short cycle delay, off-cooling stage is disabled