Table 10: Menu navigation
Menu
Submenu
Parameters displayed
Conditions for parameter
displayed units and range
Continuous ventilation
Yes, no
Fan off delay for heat
Seconds 0–30
Fan off delay for cool
Seconds 0–30
Pre-filter differential pressure
in w.c
Final filter differential pressure
in w.c
Maximum airflow
cfm / 0–100,000
UV light installed
No, yes
UV light lifetime
Hours / 0–20,000
Pickup gain
0–100
Demand
ventilation
setup
Supply fan manual bypass
Off, on
Supply fan command
Off, on
Fan % command
%
Supply fan accumulated runtime
Hours
Supply fan number times on
Counts
Operating fan request
Off, on
Fan request source
Unreliable, local input, network sensor, high
priority, BAS override, input not available
Fan VFD1 accumulated runtime
Hours
Fan VFD1 number of times on
Counts
Fan VFD2 accumulated runtime
Hours
Fan VFD2 number of times on
Counts
Isolation damper 1 status
Close, open
Isolation damper 2 status
Close, open
Demand
ventilation
service
(page 1 of 2)
Supply fan motor control
Primary, redundant
Air proving switch
Off, on
Air proving switch 2
Off, on
Supply fan VFD 1 fault
Normal, alarm
Supply fan VFD 2 fault
Normal, alarm
Discharge air static pressure
in w.c
Discharge air high duct pressure
Normal, alarm
Discharge air differential pressure
in w.c
Discharge air VP sensor alarm
Normal, alarm
Return air VP sensor alarm
Normal, alarm
Return fan pressure sensor alarm
Normal, alarm
UV light runtime
Hours
UV light needs service
Normal, alarm
UV light runtime reset
Off, reset
Demand
ventilation
Click on >> to
go to next page
for demand
ventilation
service
(page 2 of 2)
UV light runtime override
Hours / 0–100,000
Advanced Graphic Touchscreen Display on 25 Ton to 80 Ton Johnson Controls Premier Rooftop Units
36
Johnson Controls