Table 10: Menu navigation
Menu
Submenu
Parameters displayed
Conditions for parameter
displayed units and range
Heat recovery wheel status
Off, max cooling, max heating, blocking
protection, heating control, heating low limit
Supply fan command
Off, on
Econ free cooling available
No, yes
Exhaust air heat recovery temp
°F
Heat recovery wheel command
Off, on
Heat recovery wheel output
%
Energy recovery
wheel (ERW)
Heat recovery FBD command
Off, on
Exhaust type
None, barometric, modulating damper, variable
frequency fan
Exhaust damper position for exhaust fan to turn
on
% / 20–99
Exhaust damper position for exhaust fan to turn
Off
% / 10–89
Building pressure setpoint
iwg / -0.25 to 0.25
Exhaust fan manual bypass
Off, on
Demand
ventilation
exhaust setup
Pickup gain
0–100
Exhaust fan status
Off-idle, on-normal command, off-disabled, off-
VFD fault, off-low building static pressure, off-
economizer damper position
Exhaust fan command
Off, on
Building static pressure
in w.c
Exhaust damper % command
%
Exhaust flow value
cfm
Power ex VFD
Off, on
Exhaust fan VFD % command
%
Exhaust fan accumulated runtime
Hours
Exhaust fan VFD1 fault
Normal, alarm
Exhaust fan VFD2 fault
Normal, alarm
Exhaust air differential pressure
in w.c
Demand
ventilation
exhaust service
Exhaust fan motor control
Primary, redundant
Return fan installed
False, true
Return fan pressure high setpoint
in w.c (0-5)
Return fan pressure low setpoint
in w.c (0-5)
Building pressure setpoint
in w.c (-0.25 to 0.25)
Exhaust fan manual bypass
Off, on
Demand
ventilation
return fan setup
Return fan diff flow setpoint
in w.c (-0.25 to 0.25)
Exhaust flow value
cfm
Building static pressure
in w.c
Return fan VFD percent command
%
Exhaust damper % command
%
Return fan command
Off, on
Return air differential pressure
in w.c
Operating return fan flow setpoint
cfm
Return fan motor control
Primary, redundant
Return fan VFD 1 fault
Normal, alarm
Demand
ventilation
Demand
ventilation
return fan
service
Return fan VFD 2 fault
Normal, alarm
Update status
Backup file name
Backup configuration
USB functions
Insert USB
drive on the
controller for
data import and
export functions Restore from backup configuration