background image

Table 10: Menu navigation

Menu

Submenu

Parameters displayed

Conditions for parameter

displayed units and range

Full clone
Restore factory defaults
Export trend

USB functions

Insert USB

drive on the

controller for

data import and

export functions Unit nomenclature

Displays the 49 digit model number of the

selected unit

Open PDF

Insert a USB drive on either of the USB ports

available on the display

Displays any PDF document stored on the USB

drive. Enter file name as is to open the PDF

document

Alarms

Displays all and active alarms by severity,

description, and time stamp

Status

Smoke control, unit status, control board status

Summary

Overview of sensor status and unit level

information including model and serial number

information

Commissioning

Air balance, commissioning mode, network setup,

twinning, manual adjustments

Controller

Network, firmware, network inputs and time sub-

menus

Details

Displays setup and service level information for

cooling, heating, supply fan, economizer, exhaust/

return fan, mutli-zone VAV, humidity control and

load shed

Startup wizard

Displays all steps to run the start-up wizard

Trend

Displays trends for cooling, heating, fan, sensors,

economizer features and provides fault status and

diagnostics

Set schedule

Provides the capability to set up occupancy

schedules

Device list

Shows all devices connected on the common

BACnet MS/TP bus

Settings

Communication protocol settings, software

updates for MAP

MAP gateway

(submenus and

functionality

may vary for

controllers

other than

Applied Smart

Equipment

controllers)

Admin

Change MAP password, log out

Settings

Controller

address

Displays device ID, device name, BACnet

parameters of the controller; parameters

displayed are for the controller selected to view in

case of more than one controllers connected in a

daisy chain

Building static pressure
Effective zone temperature
Discharge air temperature
Return air temperature
Mixed air temperature
Effective ZNH src (zone humidity source)
Discharge air static pressure

Graphs

(page 1 of 2)

Supply fan output
Return air enthalpy
Outdoor air enthalpy
Exhaust return fan output

Graphs

Click on >>

to go to next

page for graphs

(page 1 of 2)

Cooling staged percent command

Advanced Graphic Touchscreen Display on 25 Ton to 80 Ton Johnson Controls Premier Rooftop Units

38

Johnson Controls

Summary of Contents for Advanced Graphic Touchscreen Display

Page 1: ...A 921 Supersedes 5795595 JIM A 1120 Installation Guide Issue Date 2021 09 28 Johnson Controls Advanced Graphic Touchscreen Display on 25 Ton to 80 Ton Johnson Controls Premier Rooftop Units Installati...

Page 2: ...2 Advanced Graphic Touchscreen Display on 25 Ton to 80 Ton Johnson Controls Premier Rooftop Units Johnson Controls...

Page 3: ...multiple controllers 15 Operating the display 17 Introduction 17 Key concepts 17 Display 17 Operate the touchscreen 17 Using the display 17 Procedure overview 18 Detailed procedures 19 System settings...

Page 4: ...4 Advanced Graphic Touchscreen Display on 25 Ton to 80 Ton Johnson Controls Premier Rooftop Units Johnson Controls...

Page 5: ...utlines the main sections 2 Key concepts Describes background information necessary to perform or understand specific tasks 3 Procedure overview Describes general steps for performing the tasks descri...

Page 6: ...l in a wall mounted enclosure or in a remote control panel as part of the existing workstation setup Figure 1 Touchscreen display mounted on control panel Features The display is intuitive simple to l...

Page 7: ...oard is referred to as controller and the MAP Gateway tool is referred to as MAP The Applied Smart Equipment controller is only provided on the Premier line of rooftop units Display configurations Eac...

Page 8: ...terface must be replaced with the touchscreen display in the field contact the factory for further information Key concepts Mounting options Mount the display remote in an existing control panel or on...

Page 9: ...ovided with the display unit The SA or FC bus adapter is required at the controller for communications with the display The SA adapter is required when only one controller is integrated with the displ...

Page 10: ...2 Serial port position to SA FC Bus connection Serial port position SA Bus connection FC Bus connection 1 2 2 2 2 2 3 1 1 4 1 1 5 NA NA 6 3 3 7 NA NA 8 shield NA 4 Advanced Graphic Touchscreen Display...

Page 11: ...24 VDC supply voltage to power up the display To extend the serial communications cable in order to view field bus devices 1 The display can integrate multiple field bus devices on Metasys systems Fac...

Page 12: ...where wire connections can be made and display parameters can be viewed from a floor level Mount the display box on a dry surface Avoid prolonged exposure to direct sunlight to prevent the risk of ov...

Page 13: ...the display Use one of the removable slots provided on the box to run cable back to the controller Note Refer to the sections Cabling a display with a single controller and Cabling a display with mult...

Page 14: ...gasket is applied is 0 004 in Figure 10 Cutout and display clearances Note A Display B Installation cutout Cabling a display with a single controller Figure 11 shows the connections made to the displa...

Page 15: ...when the unit is without a factory installed MAP For SA and FC bus cable recommendations and controller terminal block information refer to the BACnet Integration Setup section in the Johnson Controls...

Page 16: ...to the MAP Terminate the RJ 45 cable on the display from the MAP in any of the available ETH0 ETH1 ETH2 ports This guide shows the RJ 45 cable connected to the ETH2 port on the display Note Refer to...

Page 17: ...d design The display is a glass projected capacitive touchscreen with 10 1 in wide screen and 1280 x 800 pixels The interface on the touchscreen display supports multi touch gesture programming Figure...

Page 18: ...r sensors connected to the unit USB functions Provides the ability to do backup restore export data and clone Table 4 Display touch commands Motion Finger action Description Tap Tap on the touchscreen...

Page 19: ...ee the Detailed procedures in this chapter for further instructions for all of the tasks above Detailed procedures Table 6 Icons Icon Icon description Edit Login Settings Alarm USB functions System se...

Page 20: ...and password from Table based on the level of access desired 1 The display requires users to set a new user name and password after the first time logging in as one of the accounts in Table Advanced...

Page 21: ...tapping on the downward arrow next to the login Admin icon and selecting sign out Figure Table 7 User level restrictions User name and password Access level Descriptions admin admin Read write User co...

Page 22: ...igure tap on the Search icon to scan for controllers available on the SA FC BACnet MS TP bus 2 After the search device discovery is complete the Dev ID of available controllers appears in the drop dow...

Page 23: ...en Figure 2 The unit display configuration matches the actual unit configuration The graphical display instantly adapts to the unit sequence of operation to give the user an enhanced visual experience...

Page 24: ...for connected controller enclosed cabinet Figure 21 Home page for connected controller cutaway cabinet Advanced Graphic Touchscreen Display on 25 Ton to 80 Ton Johnson Controls Premier Rooftop Units...

Page 25: ...nect Note The MAC addresses are printed on the back of the MAP 5 To connect use the password Map YYYYYY where YYYYYY is the last six digits or characters of the MAC address of the Ethernet port Figure...

Page 26: ...outed through an Ethernet switch Check with Building IT management for an available IP Address For questions related to MAP security certificates refer to the document Installing and Using Private Key...

Page 27: ...be 192 168 0 XX XX should be a value other than 12 20 Enter the Network Subnet Mask and Gateway address which are the same as the MAP configuration from Step 13 Tap Save on the top of the screen 21 Ta...

Page 28: ...ted location The wireless connection on the MAP allows the user to access the MAP menu by using Wi Fi feature It allows users to be up to 100 ft or 31 m line of sight away indoors and up to 300 ft or...

Page 29: ...een Flicker Off Receiving data On steady Transmitting data Flicker Data transmission Ethernet Green On steady Off Communication not established On steady Communication established Flicker Data transmi...

Page 30: ...navigation structure For a complete menu structure with parameters units and ranges see Table 10 Figure 30 Display navigation structure Advanced Graphic Touchscreen Display on 25 Ton to 80 Ton Johnso...

Page 31: ...ply fan reset zone temp reset external Heating discharge air temp upper setpoint F 86 135 Heating discharge air temp lower setpoint F 85 134 Outside air temperature reset setpoint upper F 61 131 Outsi...

Page 32: ...ture off low supply voltage off high pressure lockout off low pressure lockot off freeze condition off anti short cycle delay off cooling stage is disabled Compressor 1C status Off idle on minimum on...

Page 33: ...reset setpoint lower F 50 80 Supply fan DAT setpoint high threshold 0 100 Supply fan DAT setpoint low threshold 0 100 Compressor 1A enabled Yes no Compressor 1B enabled Yes no Compressor 1C enabled Ye...

Page 34: ...1D Off on Condenser fan 2A Off on Condenser fan 2B Off on Condenser fan 2C Off on Condenser fan 2D Off on Minimum runtime for a cooling stage Minutes 3 10 Rapid start time limit Minutes 0 15 Cool Cool...

Page 35: ...free cooling is active miinimum position test comfort ventilation low OA ambient Econ free cooling available No yes Economizer damper command Supply air temperature F Operational outside air temperatu...

Page 36: ...s on Counts Fan VFD2 accumulated runtime Hours Fan VFD2 number of times on Counts Isolation damper 1 status Close open Isolation damper 2 status Close open Demand ventilation service page 1 of 2 Suppl...

Page 37: ...aust fan VFD command Exhaust fan accumulated runtime Hours Exhaust fan VFD1 fault Normal alarm Exhaust fan VFD2 fault Normal alarm Exhaust air differential pressure in w c Demand ventilation exhaust s...

Page 38: ...artup wizard Displays all steps to run the start up wizard Trend Displays trends for cooling heating fan sensors economizer features and provides fault status and diagnostics Set schedule Provides the...

Page 39: ...s page 1 of 2 Effective OAT source Note For parameter definitions refer to the Johnson Controls Premier Rooftop Units Start Up and Operation Guide 5881375 JSG A To view parameters or functionality tha...

Page 40: ...a user adjustable point value Modifications to setpoints are saved based on the most recent adjustment regardless of the device display or MAP that was used Read and write capability assigned to the...

Page 41: ...e and reset lockouts performed and cycle controller power for normal operation to resume Service priority Soft lockout Requires conditions to return to a normal range for normal operation to resume an...

Page 42: ...ort and export To read documents complete the following steps 1 Navigate to the configuration page by tapping on the Settings icon on the display 2 Connect a USB drive to either of the USB ports on th...

Page 43: ...keep folders related to the backup on the USB drive When multiple folders are available this feature does not work Restore Factory Defaults can be used to restore factory defaults in the controller Th...

Page 44: ...on the MAP icon Check that the MAP and display IP settings are configured correctly Not able to connect to MAP MAP browser on mobile laptop or tablet display Check that the MS TP bus is connected on t...

Page 45: ...ols Premier Rooftop Units Start Up and Operation Guide 24 10737 16 Getting Started with MAP Gateway 24 10737 8 Installing and Wiring MAP Gateway LIT 12011999 Using MAP Gateway LIT 12012015 Installing...

Page 46: ...screen display a wall box for indoor installation 24 VDC power supply 3 prong power cord and a touchscreen display Includes the following for the MAP installation a MAP device Does not include communi...

Page 47: ...ifications SA Bus RS 485 connector field installed 22 AWG stranded 5 wire two twisted pair shielded cable FC Bus RS 485 connector field installed 22 AWG stranded 5 wire two twisted pair shielded cable...

Page 48: ...display a 24 VDC power supply and 3 prong power cable shall be provided Refer to Figure 5 for wiring information Communication wire is to be supplied and installed in the field by others Advanced Gra...

Page 49: ...ble 18 Kit number 2TS0402 Line item Part number Description Quantity Unit 10 5882845 Graphic display W 281 9 mm H 198 1 mm TFT 1 PCS 20 5523538 Mount adv disp remote mntg 1 PCS 30 5514233 PSU In 88 26...

Page 50: ...s follows Single point 25 ton to 50 ton is 1 PTB Dual point 40 ton to 50 ton is 100 PTB Dual point 25 ton to 30 ton is 100 PTB 2021 Johnson Controls All rights reserved Subject to change without notic...

Reviews: