Note:
The following steps are only
applicable to Applied Smart Equipment
controllers.
2. This screen gives the user the ability to do
multiple tasks, such as backup controller
firmware, restore backup, upload display
software, full partial cloning, and export data.
Unit nomenclature is also displayed here
(Figure ).
3. Plug in a USB drive to the controller of the
respective unit to export or import data.
Ensure the correct controller is selected from
the Device Discovery page.
To restore data from an existing backup saved
on the USB drive, tap on
Restore
from Backup
Configuration. Then choose the .csv file to restore.
Note:
Only keep folders related to the backup
on the USB drive. When multiple folders are
available, this feature does not work.
Restore Factory Defaults can be used to restore
factory defaults in the controller.
The Export Trend option requires the user to plug a
USB drive to the controller to collect data.
Note:
For detailed information on cloning a
controller, refer to the
Johnson Controls Premier
Rooftop Units Start-Up and Operation Guide
(5881375-JSG-A).
Steps to be followed are similar
to the Smart Equipment controller being used
today.
Figure 35: USB functions
Display faults and diagnosis
Table 12 provides a list of common faults that may
be seen on the display, along with a diagnosis to
correct these errors.
Advanced Graphic Touchscreen Display on 25 Ton to 80 Ton Johnson Controls Premier Rooftop Units
43
Johnson Controls