background image

Published in U.S.A.

www.johnsoncontrols.com

BD-1300 Control Dampers Installation Instructions

 5

Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.

All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.

Building Efficiency

507 E. Michigan Street, Milwaukee, WI  53202

Actuators

For dampers using a single actuator, install the 
direct-mount actuator or associated actuator linkage to 
the linkage side of the preferred drive blade shown in 
Table 1 and Table 2. The ideal situation is to use a 
drive blade near the center of the damper height to 
distribute the torque evenly. Use only odd numbered 
blades for dampers with opposed blade rotation.

The actuators may be installed frame mounted inside 
the duct (Figure 10) or wall mounted outside the duct at 
locations indicated.

Attach one actuator to the preferred driving blade on 
the linkage side of each damper section. Refer to the 
appropriate actuator literature for proper damper sizing 
information.

For frame mount actuator drives, when two sections 
are coupled horizontally, the ideal situation is to mount 
the actuator in the air stream at the junction of the two 
damper sections as shown in Figure 11.

Table 1:  Single Actuator Location

Height, in.

Location

24 or less

Blade No. 1 or 3

 24 but 

 48

Blade No. 3 or 5

 48 but 



76

Blade No. 5 or 7

Table 2:  Multiple Actuator Location

Height, in.

Location

30

Blade Nos. 3 and 5



30 but 



48

Blade Nos. 3 and 7



48 but 



76

Blade Nos. 3 and 9

Figure 11: Actuator Bracket Location

European Single Point of Contact:

NA/SA Single Point of Contact:

APAC Single Point of Contact:

JOHNSON CONTROLS
WESTENDHOF 3
45143 ESSEN
GERMANY

JOHNSON CONTROLS
507 E MICHIGAN ST
MILWAUKEE WI 53202
USA

JOHNSON CONTROLS
C/O CONTROLS PRODUCT MANAGEMENT
NO. 22 BLOCK D NEW DISTRICT
WUXI JIANGSU PROVINCE 214142
CHINA

Reviews: