Figure 6: Connecting one AC supply to several

transmitters

Completing the installation

About this task:

Install the cover on the mounting base:

1. Slide the bottom of the cover onto the tabs at the

bottom of the mounting base.

2. Tilt the top of the cover toward the mounting base.
3. Insert the locking screw on the top of the

transmitter and secure the locking screw with a No.

1 Phillips-head screwdriver.

Result

If power is supplied to the screw terminals, the transmitter

starts when you close the cover.

Setup and adjustments

Commissioning

CD-W00-x0-2 Series Wall Mount CO

2

 and Temperature

Transmitters are factory-calibrated for the following:
• output signal, 0 to 10 V and 4 to 20 mA, proportional to

CO

2

 concentration, 0 to 2,000 parts per million (ppm)

• altitude range of 0 to 2,000 ft (0 to 600 m) without

compensation

For altitudes above 2,000 ft (600 m) where optimum

accuracy of the CO

2

 concentration measurement is

essential, modify the Building Automation System (BAS)

controller’s analog input (AI) high range to compensate

for sensor placement at other than the standard

calibration altitude.
To do this, reset the 2,000 ppm value using the controller’s

compensation factor (CF) shown in Figure 7 or Figure 8.
Calculate the corrected value:
Corrected Value = CF x 2,000
For example, if the sensor is situated at an altitude of 3,000

ft (914.4 m) above sea level, the CF is 1.10. See Figure 7 or

Figure 8. The corrected value is:
Corrected Value = 1.10 x 2,000 ppm = 2,200 ppm

Note: 

For altitude compensation, only adjust the AI

high range. The AI low range should remain at zero.

Figure 7: Altitude compensation, feet above sea level

Figure 8: Altitude compensation, meters above sea

level

Troubleshooting

About this task:

The CO

2

transmitter is not field repairable. In the event the

unit is not functioning correctly, identify the symptoms

and determine a solution:

1. Verify that the unit is mounted correctly.
2. Verify that all wiring is correct.
3. Verify that the power supply voltage level is20 to 30

VAC or 18 to 30 VDC.

Result

If the CO

2

transmitter does not operate after completing

these steps, replace the unit.

Repair information

If the CD-W00-x0-2 Series Wall Mount CO

2

 and

Temperature Transmitters fail to operate in their

specifications, replace the units. For a replacement

CO

2

transmitter, contact the nearest Johnson Controls®

representative.

CD-W00-x0-2 Series Wall Mount CO

2

 and Temperature Transmitters Installation Guide

4

Summary of Contents for CD-W00-0-2 Series

Page 1: ...uire de brouillage et 2 L utilisateur de l appareil doit accepter tout brouillage radioélectrique subi même si le brouillage est susceptible d en compromettre le fonctionnement Installation Important The CD W00 x0 2 Series Wall Mount CO2 and Temperature Transmitters are intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the transmitter could...

Page 2: ... a cable ferrule to the cable end If the distance between the sensor and the controller is over 3 meters 9 8 feet use shielded cable Connect the shield at the controller end of the cable Location selection When mounting wall model transmitters Select a location that represents the area of interest Do not install the transmitter on the ceiling Avoid placing the transmitter near heat and moisture so...

Page 3: ...ts on the top or bottom side of the printed circuit board Failure to follow proper wiring procedures may cause the transmitter to fail 2 Connect the wires to the mounting base screw terminals as shown in Figure 4 Figure 4 Screw terminals Note The transmitter generates both voltage and current output Each output has its own individual positive screw terminal Power supply requirements The transmitte...

Page 4: ...eset the 2 000 ppm value using the controller s compensation factor CF shown in Figure 7 or Figure 8 Calculate the corrected value Corrected Value CF x 2 000 For example if the sensor is situated at an altitude of 3 000 ft 914 4 m above sea level the CF is 1 10 See Figure 7 or Figure 8 The corrected value is Corrected Value 1 10 x 2 000 ppm 2 200 ppm Note For altitude compensation only adjust the ...

Page 5: ... mA and 0 to 10 VDC Maximum output current 21 mA maximum output voltage 11 V Resolution of analog outputs 0 3 ppm CO2 External load Minimum 1 000 ohms load resistance for 0 to 10 V Maximum 600 ohm load resistance for 4 to 20 mA Power supply range 24 VAC 20 50 60 Hz 18 to 30 VDC Class 2 Power consumption 1 0W Average excluding current output consumption Current consumption 100 mA peak on AC power 4...

Page 6: ...ht Dieser Sensor Transmitter kann nur wandmontiert eingesetzt werden Der elektrische Anschluß ist nach den örtlichen Vorschriften durch autorisiertes Personal durchzuführen Versorgungsspannung und Niederspannung sind getrennt zuzuführen Bei Verwendung von flexiblen Leitungen sind Kabelschuhe zu verwenden Überprüfen Sie alle Kabelverbindungen bevor Sie den Antrieb einschalten Der Kontakt mit Kompon...

Page 7: ...nslutningen ska utföras av behörig personal i enlighet med de lokala föreskrifterna Försörjningsspänning och lågspänning ska tillföras åtskilt Vid användning av flexibla ledningar ska kabelskor användas Kontrollera alla kabelförbindelser innan du tillkopplar ställdonet Kontakt med komponenter med farlig spänning kan ge elektriska stötar som kan orsaka allvarliga eller livshotande personskador Kort...

Page 8: ...ь причиной несчастного случая или повреждения оборудования если кабель между Датчик и контроллером составляет более 3 метров то должен быть экранирован Экран следует заземлять в одной точке на стороне контроллера Сохраните этот документ Portuguese Certifique se que a fonte de alimentação é compatível com a fonte de alimentação especificada na secção de Especificação Técnica Este sensor transmissor...

Page 9: ...s com techterms Your use of this product constitutes an agreement to such terms Patents Patents https jcipat com Contact information Contact your local branch office www johnsoncontrols com locations Contact Johnson Controls www johnsoncontrols com contact us Single point of contact APAC Europe NA SA JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 32 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PR...

Page 10: ... 2021 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice ...

Reviews: