129098-UIM-G-0411
Johnson Controls Unitary Products
25
TABLE 9:
Blower Performance CFM - Downflow Without Filters
STANDARD HEATING BLOWERS
Speed
Tap
EXTERNAL STATIC PRESSURE, INCHES WC (kPa)
BTU/H (kW)
Input / Output
Nominal
CFM(m³/min)
Cabinet
Size
0.1 (0.025)
0.2 (0.050)
0.3 (0.075)
0.4 (0.099)
0.5 (0.124)
cfm cm/m
cfm cm/m
cfm cm/m
cfm cm/m
cfm cm/m
56/45 (16.4/13.1)
1305 (37)
A
High No Coil
1425
40.4
1380
39.1
1305
37.0
1245
35.3
1180
33.4
High w/Coil
1385
39.2
1315
37.3
1260
35.7
1200
34.0
1135
32.2
Low No Coil
1250
35.4
1205
34.1
1145
32.4
1085
30.7
1030
29.2
Low w/Coil
1235
35.0
1190
33.7
1135
32.2
1080
30.6
1015
28.8
70/56 (20.5/16.4)
1305 (37)
A
High No Coil
1425
40.4
1380
39.1
1305
37.0
1245
35.3
1180
33.4
High w/Coil
1385
39.2
1315
37.3
1260
35.7
1200
34.0
1135
32.2
Low No Coil
1250
35.4
1205
34.1
1145
32.4
1085
30.7
1030
29.2
Low w/Coil
1235
35.0
1190
33.7
1135
32.2
1080
30.6
1015
28.8
77/62 (22.5/18.5)
1305 (37)
A
High No Coil
1425
40.4
1380
39.1
1305
37.0
1245
35.3
1180
33.4
High w/Coil
1385
39.2
1315
37.3
1260
35.7
1200
34.0
1135
32.2
Low No Coil
1250
35.4
1205
34.1
1145
32.4
1085
30.7
1030
29.2
Low w/Coil
1235
35.0
1190
33.7
1135
32.2
1080
30.6
1015
28.8
90/72 (26.3/21.1)
1305 (37)
A
High No Coil
1425
40.4
1380
39.1
1305
37.0
1245
35.3
1180
33.4
High w/Coil
1385
39.2
1315
37.3
1260
35.7
1200
34.0
1135
32.2
Low No Coil
1250
35.4
1205
34.1
1145
32.4
1085
30.7
1030
29.2
Low w/Coil
1235
35.0
1190
33.7
1135
32.2
1080
30.6
1015
28.8
7900 - 7751 AC/ACCESSORY BLOWER
Speed
Tap
EXTERNAL STATIC PRESSURE, INCHES WC (kPa)
BTU/H (kW)
Input / Output
Nominal
CFM(m³/min)
Cabinet
Size
0.1 (0.025)
0.2 (0.050)
0.3 (0.075)
0.4 (0.099)
0.5 (0.124)
cfm cm/m
cfm cm/m
cfm cm/m
cfm cm/m
cfm cm/m
56/45 (16.4/13.1)
1725 (48.9)
A
High w/Coil
1800
51.0
1760
49.9
1725
48.9
1680
47.6
1650
46.7
Med High w/Coil
1535
43.5
1505
42.6
1480
41.9
1445
40.9
1410
39.9
Med Low w/Coil
1270
36.0
1240
35.1
1215
34.4
1185
33.6
1100
31.2
Low w/Coil
1085
30.7
1055
29.9
1025
29.0
1005
28.5
980
27.8
70/56 (20.5/16.4)
1725 (48.9)
A
High No Coil
1800
51.0
1760
49.9
1725
48.9
1680
47.6
1650
46.7
High w/Coil
1535
43.5
1505
42.6
1480
41.9
1445
40.9
1410
39.9
Low No Coil
1270
36.0
1240
35.1
1215
34.4
1185
33.6
1100
31.2
Low w/Coil
1085
30.7
1055
29.9
1025
29.0
1005
28.5
980
27.8
77/62 (22.5/18.5)
1725 (48.9)
A
High No Coil
1800
51.0
1760
49.9
1725
48.9
1680
47.6
1650
46.7
High w/Coil
1535
43.5
1505
42.6
1480
41.9
1445
40.9
1410
39.9
Low No Coil
1270
36.0
1240
35.1
1215
34.4
1185
33.6
1100
31.2
Low w/Coil
1085
30.7
1055
29.9
1025
29.0
1005
28.5
980
27.8
90/72 (26.3/21.1)
1725 (48.9)
A
High No Coil
1800
51.0
1760
49.9
1725
48.9
1680
47.6
1650
46.7
High w/Coil
1535
43.5
1505
42.6
1480
41.9
1445
40.9
1410
39.9
Low No Coil
1270
36.0
1240
35.1
1215
34.4
1185
33.6
1100
31.2
Low w/Coil
1085
30.7
1055
29.9
1025
29.0
1005
28.5
980
27.8
TABLE 10:
AC Accessories
MODEL NO.
DESCRIPTION
USED WITH
7900-7761
AC CONTROL KIT
A/C RELAY FOR DGPH MODELS
7900-7741/A
4 TON BLOWER
4 TON, 2 SPEED BLOWER FOR DGPH, DGPA
7900-7751
5 TON BLOWER
5 TON, 4 SPEED BLOWER FOR ALL MODELS
1PS0166
HIGH ALTITUDE KIT FOR NATURAL GAS
ALL MODELS
1PS0167
HIGH ALTITUDE KIT FOR PROPANE (LP) GAS
ALL MODELS