288591-BIM-C-0408
Johnson Controls Unitary Products
3
Installation
Limitations
These units must be installed in accordance with the following
national and local safety codes.
1.
National Electrical Code ANSI/NFPS No. 70 or Canadian
Electrical Code Part 1, C22.1 (latest editions).
2.
Local plumbing and waste water codes and other
applicable local codes.
Refer to Table 6 for unit physical data and to Table 5 for electrical
data.
If components are to be added to a unit to meet local codes,
they are to be installed at the dealer's and/or the customer's
expense.
Size of unit for proposed installation should be based on heat
loss/heat gain calculations made in accordance with industry
recognized procedures identified by the Air Conditioning
Contractors of America.
Figure 1: Component Location
Direct Drive Condenser
Fan Motor
Highly Efficient Enhanced Copper
Tube/Aluminum Fin Indoor Coil
Highly Efficient Enhanced Copper
Tube/Aluminum Fin Outdoor Coil
Decorative Protective
Coil Guard
ECM Direct Drive Blower Motor With
Slide-Out Blower Assembly
Heavy Gauge
Removable Base Rails
High-Efficiency Compressor
Rigidly Mounted
Long-Lasting
Powder Paint Finish
Low Voltage
Terminal Block
High Voltage
Terminal Block
Back And Bottom
Return Air and Supply
Air Duct Opening
Table 1:
Unit Limitations
Size
(Tons)
Model
Unit Voltage
Unit Limitations
Applied Voltage
Outdoor DB Temp
Min
Max
Max (°F)
024
(2.0)
DPX
208/230-1-60
187
252
115
030
(2.5)
DPX
208/230-1-60
187
252
115
036
(3.0)
DPX
208/230-1-60
187
252
115
208/230-3-60
187
252
115
460-3-60
432
504
115
042
(3.5)
DPX
208/230-1-60
187
252
115
208/230-3-60
187
252
115
460-3-60
432
504
115
048
(4.0)
DPX
208/230-1-60
187
252
115
208/230-3-60
187
252
115
460-3-60
432
504
115
060
(5.0)
DPY
208/230-1-60
187
252
115
208/230-3-60
187
252
115
460-3-60
432
504
115