288591-BIM-C-0408
Johnson Controls Unitary Products
15
042
(3.5)
DPX
1100
0.03
0.01
0.03
0.05
1200
0.04
0.02
0.03
0.06
1300
0.04
0.03
0.03
0.07
1400
0.04
0.04
0.03
0.08
1500
0.05
0.05
0.04
0.09
1600
0.06
0.06
0.05
0.10
048
(4.0)
DPX
1100
0.03
0.01
0.03
0.05
1200
0.04
0.02
0.03
0.06
1300
0.04
0.03
0.03
0.07
1400
0.04
0.04
0.03
0.08
1500
0.04
0.05
0.04
0.09
1600
0.04
0.06
0.05
0.10
1700
0.05
0.07
0.05
0.11
1800
0.05
0.07
0.06
0.11
1900
0.06
0.08
0.06
0.11
2000
0.07
0.08
0.07
0.12
060
(5.0)
DPY
1100
0.03
0.01
0.03
0.05
1200
0.04
0.02
0.03
0.06
1300
0.04
0.03
0.03
0.07
1400
0.04
0.04
0.03
0.08
1500
0.04
0.05
0.04
0.09
1600
0.04
0.06
0.05
0.10
1700
0.05
0.07
0.05
0.11
1800
0.05
0.07
0.06
0.11
1900
0.06
0.08
0.06
0.11
2000
0.07
0.08
0.07
0.12
1. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the
return air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Table 10: Electric Heat Minimum Supply Air
Size
(Tons)
Model
Voltage
Minimum Supply Air (CFM)
Heater kW
5.0
7.5
10.0
15.0
20.0
25.0
024
(2.0)
DPX
208/230-1-60
630
630
800
-
-
-
030
(2.5)
DPX
208/230-1-60
630
630
800
800
-
-
036
(3.0)
DPX
208/230-1-60
1070
1070
1070
1070
-
-
208/230-3-60
1070
1070
1070
1070
-
-
460-3-60
1070
1070
1070
1070
-
-
042
(3.5)
DPX
208/230-1-60
1225
1225
1225
1225
-
-
208/230-3-60
1225
1225
1225
1225
-
-
460-3-60
1225
1225
1225
1225
-
-
048
(4.0)
DPX
208/230-1-60
-
-
1200
1430
1430
1430
208/230-3-60
-
-
1200
1430
1430
1430
460-3-60
-
-
1200
1430
1430
1430
060
(5.0)
DPY
208/230-1-60
-
-
1615
1615
1955
1955
208/230-3-60
-
-
1615
1615
1955
1955
460-3-60
-
-
1615
1615
1955
1955
Table 9:
Additional Static Resistance (Continued)
Size
(Tons)
Model
CFM
Wet Indoor Coil
Economizer
1
Filter/Frame Kit
Electric Heat
Table 11: Indoor Blower Specifications
Size
(Tons)
Model
Motor
HP
RPM
Eff.
SF
Frame
024
(2.0)
DPX
1/2
Variable
0.8
1.0
48
030
(2.5)
DPX
1/2
Variable
0.8
1.0
48
036
(3.0)
DPX
1/2
Variable
0.8
1.0
48
042
(3.5)
DPX
3/4
Variable
0.8
1.0
48
048
(4.0)
DPX
3/4
Variable
0.8
1.0
48
060
(5.0)
DPY
1
Variable
0.8
1.0
48
Table 12: Electric Heat Multipliers
Voltage
kW Capacity Multipliers
1
1. Electric heaters are rated at nominal voltage. Use this table to
determine the electric heat capacity for heaters applied at
lower voltages.
Nominal
Applied
240
208
0.75
230
0.92
480
460
0.92