Network Room Module Technical Bulletin
31
Specifications and Ordering Codes
Specifications and Technical Data
Table 11: Network Room Module Specifications and Technical Data
Parameter/Component Value/Description
Power Supply
LP-NRM0xx-000C Series
14.3 to 27.6 VDC (15 to 18 VDC from connected FX controller)
at 500 mW maximum, or
24 VAC ± 15%, 50/60 Hz, 1 VA maximum
Class 2 or Safety Extra-Low Voltage (SELV)
Power Supply
LP-NRM5xx-000C and
LP-NRM6xx-000C Series
9.8 to 16.5 VDC (15 VDC nominal) at 35 mA maximum
Class 2 or Safety Extra-Low Voltage (SELV)
Ambient Operating
Conditions
0 to 50°C (32 to 122°F)
10 to 90% RH noncondensing (and maximum 30°C [86°F] dew point)
Ambient Storage
Conditions
-20 to 70°C (0 to 160°F)
10 to 90% RH noncondensing (and max. 30°C [86°F] dew point)
Terminations
Terminal block with screw terminals in base for 1.5 mm
2
/16 AWG (maximum)
wires. Recommended tightening torque 0.5 N·m
Temperature Sensor
Pt1000 Class A, DIN EN 60751. Range 0 to 40°C (32 to 104°F)
Accuracy better than ±0.5°C (±0.9°F) with a display resolution of 0.5°C or 0.5°F
Suitable for residential and commercial office environments only
Display LCD
Display with three digits and six symbols (except temperature only models)
Controls
Dial and push buttons (depending on model)
Communications
Interface
Serial Bus RS-485 N2 Open Protocol at 9600 baud
Network Variable
Interface
Standard FX Platform NRM Room Sensor Object variables and attributes
Service Port
Model LP-NRM0xx: For FX Programming Key with 9 VDC power
Models LP-NRM5xx and LP-NRM6xx: For MUI with 15 VDC power
Mounting
Direct surface mount. Plastic base for surface mount with wiring conduits,
recessed wall box, and panel mounting kits available to order.
Housing
Material: ABS + polycarbonate, UL94-HB flammability rating
Protection: IP30 (CEI/EN60529)
Dimensions (H x W x D)
80 x 80 x 35 mm (3.15 x 3.15 x 1.4 in.), or
120 x 80 x 35 mm (4.72 x 3.15 x 1.4 in.)
Continued on next page . . .