IFC Networking—Metasys Intelligent Fire Network
Example 3
Ground fault detection feedthrough is effective for a maximum of
two serially connected (point-to-point) repeaters. Therefore, a maximum
of five repeaters can be connected in series when ground fault detection is
required. Figure 15 shows how the ground fault detection feedthrough
switches must be arranged in order to achieve this maximum
configuration.
on this FN segment is provided
by the MPS-24A power supply
in the left node.
Ground fault detection
on this FN segment is provided
by the MPS-24A power supply
in the right node.
On
On
On
On
On
On
Repeater
Node
Node
Off
gfd3
Ground fault detection
Repeater
Repeater Repeater Repeater
Figure 15: Maximum Point-to-Point Series Repeater
Ground Fault Feedthrough Configuration (Example 3)