background image

FlexSys

 Underfloor Air Terminal (Constant Volume)

Élan - 06R - 180

Model:

©2016 Johnson Controls   |   The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local           

                                                Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

© 2016 AirFixture, LLC

1

Installation / Operation Manual

V160829

TOOLS REQUIRED:

   1.

 Power Screwdriver (low torque setting) 

       • Phillips #3 Bit - floor panel screws

       • Allen-Head Bit (5/32" / 4mm) - retention bar center screw

   

2.

 Panel Lifter (suction cups) - remove floor panels

   3.

 Jigsaw - cut opening in floor panel (if panels are not pre-cut)

   4.

 Carpet Knife - cut opening in carpet tile / floor covering 

MATERIALS REQUIRED:

   

1.

 Élan-06R-180 Underfloor Air Terminal

   

PREPARATION:

   

1.

 Verify that the Élan-06R-180 is the correct model, unit count 

       and location(s) per scheduled placement.

   2.

 Remove the floor covering / floor panel at the desired 

       location(s) (if installed).

   

3.

 Verify that all adjacent floor panels are properly installed.

INSTALLATION:

The Élan-06R-180 is designed for drop-in installation in a floor 

panel. If the floor panel was installed with a 6"Ø [+1/8"/-0"] 

(152mm [+3.175/-.00]) round hole pre-cut, skip to 

Step 2

. If the 

unit is being added to an existing installation, begin with 

Step 1

.

IMPORTANT: When adjusting the center screw to loosen 

or tighten the retention bar, a power screw driver on a LOW 

TORQUE SETTING is recommended. Overtightening can 

warp the sliding damper plate, resulting in the inability to 

adjust air flow. 

Take care to avoid slippage of the driver bit; 

this may result in scratch damage to the diffuser grille.

   1.

 Remove the floor panel and cut a 6"Ø [+1/8"/-0"] 

       (152mm [+3.175/-.00]) round opening for the Élan terminal. 

       Cut opening in carpet tile using same dimensions / position.

       Replace floor panel / carpet tile when finished.

       

NOTE: Floor panels with pre-cut openings may be 

       supplied by flooring manufacturer.

 

   2.

 Verify that there is enough clearance between the retention 

       bar and diffuser grille to allow the collapsable arms to fold in 

       and clear the edge of the opening. If there is not enough 

       clearance, turn the center screw counter-clockwise to lower 

       the retention bar. 

   

3.

 Insert the Élan terminal into the opening in the floor panel. 

       The collapsable arms of the retention bar should fold back 

       out to their default position once the opening is cleared.

   

4.

 To secure the Élan terminal in place, tighten the 

       retention bar to the underside of the floor panel 

       by turning the center screw clockwise.

   

5.

 For protection of the grille’s finish during 

       construction, a Grille Cover is recommended.

REFER TO PAGE 2 FOR ADDITIONAL INFORMATION:

OPERATION / MAINTENANCE / PARTS

ALL DIMENSIONS N/- 0.1" (2.5mm)

6.75

171mm

6

ӯ

152mm

5.8

147mm

COLLAPSABLE

RETENTION BAR

5

127mm

Reviews: