RWF ROTARY SCREW COMPRESSOR UNITS
MAINTENANCE
S70-600 IOM (OCT04)
Page 33
VOLUMIZER
®
TRANSMITTER
REPLACEMENT - SLIDE STOP
The VOLUMIZER
®
Transmitter is located on the right side
of the compressor (facing shaft) at the inlet end (see Figure
28).
The linear transmitter with hermetic enclosure is based on
the inductive measuring principle. It features removable
electronics (from the sensor well) eliminating the need to
evacuate the compressor for replacement. This type of
transmitter is dedicated to volume ratio control and has no
user adjustments.
1.
Shut off control power.
2.
Remove DIN connector plug from transmitter.
3.
Loosen set screws.
4.
Remove transmitter unit.
5.
Install new transmitter unit.
6.
Tighten set screws.
7.
Apply DIN connector plug to transmitter.
8.
Turn on control power.
NOTE: For calibration of the Volumizer
®
unit, refer to
the Analog Calibration instructions in publication
S90-010 O.
Figure 28 - VOLUMIZER
®
TRANSMITTER
TEMPERATURE SENSOR REPLACEMENT
This device is static sensitive.
Please follow proper ESD proce-
dures when handling.
1.
Shut off control power.
2.
Remove DIN connector plug from transmitter, Figure 30.
3.
Unscrew knurled ring and remove transmitter unit.
4.
Apply thermal compound to new sensor assembly, insert
into thermal well, and tighten knurled ring.
5.
Apply DIN connector plug to transmitter.
6.
Turn on control power.
NOTE: The temperature sensor is factory set. If cali-
bration is required, refer to Analog Calibration instruc-
tions in publication S90-010 O.
OIL LEVEL TRANSMITTER
REPLACEMENT
The Oil Level Transmitter is located on the front of the sepa-
rator near the bottom/center (see Figure 29).
The linear transmitter with hermetic enclosure is based on
the capacitive measuring principle. It features removable
electronics (from the sensor well) eliminating the need to
evacuate the compressor for replacement. This transmitter is
dedicated to oil level control and has no user adjustments.
1.
Shut off control power.
2.
Remove DIN connector plug from transmitter.
3.
Loosen set screws.
4.
Remove transmitter unit.
5.
Install new transmitter unit.
6.
Tighten set screws.
7.
Apply DIN connector plug to transmitter.
8.
Turn on control power.
Figure 30 - TEMPERATURE TRANSMITTER
Figure 29 - OIL LEVEL TRANSMITTER
7.
Apply DIN connector plug to transmitter.
8.
Turn on control power.
NOTE: For calibration instructions, refer to Quantum
™
Operator's Manual, S90-010 O.