background image

FX-WRZRMT10K-0 Wireless Remote Temperature Transmitter Installation Guide

2

North American Emissions Compliance

United States 

Canada 

Installation

Follow these guidelines when installing the 
FX-WRZRMT10K-0 Wireless Remote Temperature 
Transmitter and the associated TE-6300 Series 
Temperature Sensor:

Transport the transmitter and sensor in their 
original containers to minimize vibration and shock 
damage.

Verify that all the parts shipped with the transmitter 
and sensor.

Do not drop the transmitter or sensor, or subject 
either component to physical shock.

Do not attempt to remove or repair the circuit board 
from the transmitter housing. Other than battery 
replacement, the transmitter and sensor are not 
user serviceable.

Parts Included

FX-WRZRMT10K-0 Wireless Remote Temperature 
Transmitter (includes one transmitter, one 
mounting base, and strips of double

-

sided 

adhesive foam tape; all factory assembled)

one strain relief bushing

one DIP switch overlay for a mesh network 
application using an FX-ZFR1811 Router

one DIP switch overlay for a non-mesh network, 
One-to-One application using an FX-WRZ7850-0 
Receiver

one installation instructions sheet

two AA alkaline batteries

Dimensions

See Figure 1 for dimensions and physical features of 
the FX-WRZRMT10K-0 Wireless Remote Temperature 
Transmitter and the associated TE-6300 Series 
Temperature Sensor. 

Special Tools Needed

1/16 in. (1.6 mm) Allen

-

head adjustment tool 

(Johnson Controls T-4000-119; order separately) 
for the tamper-resistant set screw that secures the 
transmitter to the mounting base

1/8 in. (3 mm) blade screwdriver for making wiring 
connections to the terminal block on the transmitter

Compliance Statement (Part 15.19)

This device complies with Part 15 of the FCC Rules. 
Operation is subject to the following two conditions:

1. This device may not cause harmful interference, 

and

2. This device must accept any interference 

received, including interference that may cause 
undesired operation.

Warning (Part 15.21)

Changes or modifications not expressly approved by 
the party responsible for compliance could void the 
user’s authority to operate the equipment.

Industry Canada Statement

The term 

IC

 before the certification/registration 

number only signifies that the Industry Canada 
technical specifications were met.

Le terme « IC » précédant le numéro d'accréditation/
inscription signifie simplement que le produit est 
conforme aux spécifications techniques d'Industry 
Canada.

Figure 1:  FX-WRZRMT10K-0 and TE-6300 

Dimensions and Physical Features, in./mm

Signal

Test Button

Tamper Resistant

Set Screw

4-23/32

120

1-1/2

38

°F/°C

Button

FI

G

:dm

ns

ns

3-5/32

80

10 ft (3 m)

Plenum-Rated Cable

3

76

1/4 in. (6 mm)

Outside Diameter

Back of Base

to Front of
Protrusion

Summary of Contents for FX-WRZRMT10K-0

Page 1: ...ter or receiver The FX WRZRMT10K 0 Transmitter and associated TE 6300 Series Temperature Sensor are designed for indoor intra building applications only IMPORTANT The FX WRZRMT10K 0 Wireless Remote Temperature Transmitter is intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the transmitter could lead to personal injury or property damage to...

Page 2: ...RMT10K 0 Wireless Remote Temperature Transmitter and the associated TE 6300 Series Temperature Sensor Special Tools Needed 1 16 in 1 6 mm Allen head adjustment tool Johnson Controls T 4000 119 order separately for the tamper resistant set screw that secures the transmitter to the mounting base 1 8 in 3 mm blade screwdriver for making wiring connections to the terminal block on the transmitter Comp...

Page 3: ...ent rooms and elevator shafts and concrete or brick walls between the transmitter and the FX ZFR1811 Router or FX WRZ7850 0 Receiver Do not mount the transmitter closer than 2 ft 0 61 m or farther than 100 ft 30 m from the FX ZFR1811 Router or 150 ft 45 m from the FX WRZ7850 0 Receiver The recommended indoor line of sight transmission range between the transmitter and the FX ZFR1811 Router is 50 f...

Page 4: ...he mounting surface by carefully twisting the base off of the surface 3 Remove the adhesive foam tape from the mounting base and clean the mounting base to remove any leftover adhesive Note New double sided adhesive foam tape is required to remount the base on the surface use Can Do National Tape Code No 99116 adhesive foam tape or its equivalent Connecting the TE 6300 Series Temperature Sensor to...

Page 5: ...ousing on its mounting base 1 Place the appropriate DIP switch overlay based on the application over the DIP switches See Figure 5 through Figure 7 IMPORTANT Do not power up the FX WRZRMT10K 0 Wireless Remote Temperature Transmitter until a receiver or controller is installed and operating within the same Radio Frequency RF range If this condition is not met the transmitter uses a higher than norm...

Page 6: ...Transmitter s are set to the same value a Set the POWER switch to OFF b Set the MODE switch to 1 to 1 c Set the SENSOR to 199 for applications with only one transmitter per controller Use the other settings for additional transmitters in applications with a single controller Refer to the One to One Wireless Sensing System Technical Bulletin LIT 12011663 for information on commissioning multiple FX...

Page 7: ...structions Part No 24 10563 20 for more information on testing signal strength Additional Product Information Table 2 includes Negative Temperature Coefficient NTC thermistor sensor temperature resistance response characteristics for the TE 6300 Series Temperature Sensor The values included in this table can be used to verify the accuracy of the temperature sensor in the field Note If another manu...

Page 8: ...he points based on the selections made in the Controller Selection screen The Zone temperature input point does not appear on the Point Assignment screen because this point is assigned to the SA Bus 10 Assign your points if needed Use the right arrow to assign a point to an object Use the left arrow to unassign a point from an object Use drag and drop functionality to move a point up and down the ...

Page 9: ... Probe Adjustable Enclosure TE 6361V 2 Johnson Controls 10k ohm Type II Thermistor Sensor 8 in 203 mm Duct Probe Flange Mount Enclosure TE 636GV 2 Johnson Controls 10k ohm Type II Thermistor Sensor 4 in 102 mm Duct Probe Flange Mount Enclosure TE 636S 1 Johnson Controls 10k ohm Type II Thermistor Sensor Strap Mount Probe FX WRZSST 110 Wireless Sensing System Tool For Use with an FX WRZRMT10K 0 Wir...

Page 10: ...ure Sensors Sensor Type 10k ohm Johnson Controls Type II Thermistor Sensor Sensor Thermal Characteristics See Table 2 Sensor Temperature Coefficient Nonlinear 10k ohm NTC Thermistor Electrical Connections 22 AWG 0 6 mm Diameter x 10 ft 3 m Long Plenum Rated Cable White Leads Probe Materials Stainless Steel Mounting Mount within 10 ft 3 m of the FX WRZRMT10K 0 Wireless Remote Temperature Transmitte...

Reviews: