FX-WRZRMT10K-0 Wireless Remote Temperature Transmitter Installation Guide
4
3. Peel off the protective paper from one side of the
factory-installed strips of adhesive foam tape on
the back of the mounting base.
4. When positioned correctly, the arrow between the
terminal slots on the inside of the mounting base
should point up. Ensure that the mounting base is
upright (tamper-resistant set screw on top) and
press the base firmly onto the clean mounting
surface.
5. See
Connecting the TE-6300 Series Temperature
Sensor to the FX-WRZRMT10K-0 Wireless
Remote Temperature Transmitter
Removing a Mounting Base Installed with
Double-Sided Adhesive Foam Tape
To remove or relocate a transmitter mounted with
double-sided adhesive foam tape:
1. Remove the transmitter housing from its mounting
2. Remove the mounting base from the mounting
surface by carefully twisting the base off of the
surface.
3. Remove the adhesive foam tape from the mounting
base and clean the mounting base to remove any
leftover adhesive.
Note:
New double-sided adhesive foam tape is
required to remount the base on the surface; use
Can
-
Do National Tape (Code No. 99116) adhesive
foam tape or its equivalent.
Connecting the TE-6300 Series Temperature
Sensor to the FX-WRZRMT10K-0 Wireless
Remote Temperature Transmitter
To connect the TE-6300 Series Temperature Sensor to
the FX-WRZRMT10K-0 Wireless Remote Temperature
Transmitter:
1. Feed the wire lead through the hole on the bottom
edge of the transmitter housing.
2. Loop the wire lead through the strain relief bushing
(included with the transmitter) as shown in
Figure 3, just inside the bottom edge of the
transmitter housing.
Note:
The strain relief bushing is designed to
accommodate wire sizes ranging from 1/16 to 3/16 in.
(2 to 5 mm) in diameter.