background image

FX-WRZRMT10K-0 Wireless Remote Temperature Transmitter Installation Guide

3

coin for unlocking the transmitter housing from the 
mounting base locking tab

Mounting

The FX-WRZRMT10K-0 Wireless Remote 
Temperature Transmitter can be surface mounted 
using the adhesive tape pieces affixed to the back of 
the transmitter. The transmitter can also be mounted 
on metal surfaces using a Johnson Controls 
MAGNET-BASE-PLW Magnetic Backplate (order 
separately).

To mount the TE-6300 Series Temperature Sensor, 
refer to the installation instructions included with the 
device.

Note:

If another manufacturer’s 10k ohm thermistor 

sensor is used with the FX-WRZRMT10K-0 Wireless 
Remote Temperature Transmitter, the sensor must be 
mounted within 10 ft (3 m) of the transmitter.

Location Considerations

When locating the temperature transmitter:

Mount the transmitter vertically, for ease of reading 
the Liquid Crystal Display (LCD) on the face of the 
unit.

Locate the transmitter on the same building level 
as the nearest FX-ZFR1811 Router or 
FX-WRZ7850-0 Receiver.

For best signal transmission, locate the transmitter 
at least 2 in. (51 mm) away from any metal 
obstructions.

Wherever possible, locate the transmitter in the 
direct line of sight to the FX-ZFR1811 Router or 
FX-WRZ7850-0 Receiver. Signal transmission is 
best if the path between the transmitter and the 
router or receiver is as direct as possible. Line of 
sight is desirable but not required, as long as the 
path is not blocked by large metal objects.

Avoid metal obstructions (including equipment 
rooms and elevator shafts) and concrete or 
brick walls between the transmitter and the 
FX-ZFR1811 Router or FX-WRZ7850-0 Receiver.

Do not mount the transmitter closer than 
2 ft (0.61 m) or farther than 100 ft (30 m) from the 
FX-ZFR1811 Router, or 150 ft (45 m) from the 
FX-WRZ7850-0 Receiver.

The recommended indoor line-of-sight 
transmission range between the transmitter and 
the FX-ZFR1811 Router is 50 ft (15 m).

Run the temperature sensor wire lead to the 
transmitter, supporting the wire lead along the way 
as necessary. This wire lead should not exceed 
10 ft (3 m) in length.

Installing the FX-WRZRMT10K-0 Wireless 
Remote Temperature Transmitter

The FX-WRZRMT10K-0 Wireless Remote 
Temperature Transmitter can be surface mounted 
using the double

-

sided adhesive foam tape 

factory-installed on the back of the device. To mount 
the transmitter base with adhesive foam tape:

1. Clean the desired mounting surface to ensure that 

the adhesive foam tape sticks to the surface.

Note:

The mounting surface, mounting base, and 

ambient temperature must be at least 50°F (10°C) 
when mounting the transmitter base with adhesive 
foam tape.

2. Remove the transmitter housing from its mounting 

base (Figure 2)

Figure 2:  Removing the Transmitter Housing

from its Mounting Base

(Reverse the Steps to Reinstall the Housing)

Tabs

1. Loosen (but do not remove)
the tamper-resistant set screw
on the locking tab of the
mounting base.

2. Insert a coin into the slot
on the top of the transmitter
housing, and depress the
locking tab on the mounting
base to release the housing.

F

IG

:tr

ns

m

ttr_

rm

vl

4. Pull the bottom of the transmitter housing
down and off the tabs on the mounting base.

3. Swing the
transmitter
housing off
the mounting
base.

Mounting

Base

Transmitter

Housing

Summary of Contents for FX-WRZRMT10K-0

Page 1: ...ter or receiver The FX WRZRMT10K 0 Transmitter and associated TE 6300 Series Temperature Sensor are designed for indoor intra building applications only IMPORTANT The FX WRZRMT10K 0 Wireless Remote Temperature Transmitter is intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the transmitter could lead to personal injury or property damage to...

Page 2: ...RMT10K 0 Wireless Remote Temperature Transmitter and the associated TE 6300 Series Temperature Sensor Special Tools Needed 1 16 in 1 6 mm Allen head adjustment tool Johnson Controls T 4000 119 order separately for the tamper resistant set screw that secures the transmitter to the mounting base 1 8 in 3 mm blade screwdriver for making wiring connections to the terminal block on the transmitter Comp...

Page 3: ...ent rooms and elevator shafts and concrete or brick walls between the transmitter and the FX ZFR1811 Router or FX WRZ7850 0 Receiver Do not mount the transmitter closer than 2 ft 0 61 m or farther than 100 ft 30 m from the FX ZFR1811 Router or 150 ft 45 m from the FX WRZ7850 0 Receiver The recommended indoor line of sight transmission range between the transmitter and the FX ZFR1811 Router is 50 f...

Page 4: ...he mounting surface by carefully twisting the base off of the surface 3 Remove the adhesive foam tape from the mounting base and clean the mounting base to remove any leftover adhesive Note New double sided adhesive foam tape is required to remount the base on the surface use Can Do National Tape Code No 99116 adhesive foam tape or its equivalent Connecting the TE 6300 Series Temperature Sensor to...

Page 5: ...ousing on its mounting base 1 Place the appropriate DIP switch overlay based on the application over the DIP switches See Figure 5 through Figure 7 IMPORTANT Do not power up the FX WRZRMT10K 0 Wireless Remote Temperature Transmitter until a receiver or controller is installed and operating within the same Radio Frequency RF range If this condition is not met the transmitter uses a higher than norm...

Page 6: ...Transmitter s are set to the same value a Set the POWER switch to OFF b Set the MODE switch to 1 to 1 c Set the SENSOR to 199 for applications with only one transmitter per controller Use the other settings for additional transmitters in applications with a single controller Refer to the One to One Wireless Sensing System Technical Bulletin LIT 12011663 for information on commissioning multiple FX...

Page 7: ...structions Part No 24 10563 20 for more information on testing signal strength Additional Product Information Table 2 includes Negative Temperature Coefficient NTC thermistor sensor temperature resistance response characteristics for the TE 6300 Series Temperature Sensor The values included in this table can be used to verify the accuracy of the temperature sensor in the field Note If another manu...

Page 8: ...he points based on the selections made in the Controller Selection screen The Zone temperature input point does not appear on the Point Assignment screen because this point is assigned to the SA Bus 10 Assign your points if needed Use the right arrow to assign a point to an object Use the left arrow to unassign a point from an object Use drag and drop functionality to move a point up and down the ...

Page 9: ... Probe Adjustable Enclosure TE 6361V 2 Johnson Controls 10k ohm Type II Thermistor Sensor 8 in 203 mm Duct Probe Flange Mount Enclosure TE 636GV 2 Johnson Controls 10k ohm Type II Thermistor Sensor 4 in 102 mm Duct Probe Flange Mount Enclosure TE 636S 1 Johnson Controls 10k ohm Type II Thermistor Sensor Strap Mount Probe FX WRZSST 110 Wireless Sensing System Tool For Use with an FX WRZRMT10K 0 Wir...

Page 10: ...ure Sensors Sensor Type 10k ohm Johnson Controls Type II Thermistor Sensor Sensor Thermal Characteristics See Table 2 Sensor Temperature Coefficient Nonlinear 10k ohm NTC Thermistor Electrical Connections 22 AWG 0 6 mm Diameter x 10 ft 3 m Long Plenum Rated Cable White Leads Probe Materials Stainless Steel Mounting Mount within 10 ft 3 m of the FX WRZRMT10K 0 Wireless Remote Temperature Transmitte...